Table should always contain data L(i) = 100%
Should the linearisation table contain less than 32 data pairs (j < 32) so the left column of the table must be closed wit 0:
L
(j < 32) = 0.
The NIVOCAP will ignore data after recognising level value”0” with the serial number other than “1”.0
If the above conditions are not fulfilled error will be indicated (see Chapter Error Codes)
6.6. S
ERVICE PARAMETERS
(
READ ONLY
)
P60: Overall operating hours of the unit (h)
Display of the elapsed time
N
UMBER OF OPERATING HOURS
I
NDICATION FORM
0 to 999,9 h
xxx,x
1000 to 9999 h
xxxx
Over 9999 h
x,xx:e represents x,xx *10
e
P61: Time elapsed after last switch-on (h)
Indication form as under
P60
6.7. T
EST PARAMETERS
P80: Current (generator) output test (mA)
Going to this parameter, the actual current output (corresponding to the measured process value) will be displayed. By pressing ENTER
E
the
(now blinking) current value can be set for any value between 3,9 and 20.5 mA. The current output has to show the same value which can be
checked by an ampere meter, according to the description under 4.4. Press ENTER
E
to quit test mode and return the parameter address
P96: b:a.aa Software code
a.aa:
Number of the software version
b:
Code of the special version