5.2. P
ROGRAMMING WITH THE
SAP-202
DISPLAY MODULE
The NIVOCAP should be adjusted to the process by programming the parameters. The SAP-200 Display Module can be used to display the parameters while
programming and measurement values during measurement.
The SAP-200 supports two separately accessible programming modes as below.
QUICKSET (See 5.2.4)
This feature is for quick programming of the 4 basic parameters like with programming without display module but aided by images on the display. Measured
values can only be displayed in percentage.
•
Assignment of min level to 4 mA
•
Assignment of max level to 20 mA
•
Damping
•
Fault indication by the current output
Full parameter programming (See 5.2.5)
Highest level programming with availability of all parameters and features such as:
•
Measurement configuration
•
Adjustment of outputs
•
Measurement optimalisation
•
11 pre-programmed tank shapes for volume calculation
•
21 pre-programmed formula for flow metering
5.2.1 SAP-202
DISPLAY MODULE
Symbols used on the LCD
::
•
LEV
– Level measurement mode
•
VOL
– Volume measurement mode
•
PROG
- Programming mode
•
FAIL
- Measurement / device error
•
- Level changing direction
•
Bargraph assigned to the level or volume
¨
°F sec min hour day
Symbols used on the frame
::
•
M
– Metric (European) system
•
US
– US (Anglo-Saxon) system
LED is
lit
•
COM
–
digital (HART) communication
ECHO
– value within the valid range