13
PMGB0126A rev.2 - 11/2006
English
UNITS INSTALLATION
10.1.2. AVAILABLE CONFIGURATION
Four different configuration are available for outdoor unit only
changing the panels and fan position.
NOTE:
Keep in mind that fan unit weight is aprox 30Kg, the unit
as well as relevant equipment covered with the vinyl cover
during installation work.
Air inlet modification
To change air inlet is only necessary to interchange the
indicated panels position. Both panels us screws to be fixed to
unit chasis.
To change air outlet is necessary to interchange panels too.
Fan outlet panel is attached to fan structure, which must be
mounted as follow
-
■
-
-
10.1.3. INSTALLATION PLACE PROVISION
Concrete Foundation
1. Foundation could be on flat and is recommended be
100-300mm higher than ground level.
2. Install a drainage around foundation for smooth drain
3. When installing the outdoor unit fix the unit by anchor bolts of
M10
4. When installing the unit on a roof or a veranda, drain water
sometimes turns to ice on a cold morning. Therefore, avoid
draining in an area that people often use because it is
slippery.
Suspended unit
1. Suspend the unit as the drawing indicates.
2. Ensure that ceiling can resist the Outdoor unit weight
indicated in specification label plate
■
■
Change Panel
Change Panel
A
B
Nº
Description
Outdoor Unit
Cut this portion of bolt If not, it’s difficult
to remove Service Cover
Mortar Hole (Ø100xDepth 150)
Anchor Bolt M10
Drainage (Wide 100xDepth 150)
Drainage
Vibration-proof rubber
Mark
Dimension
Model
5HP
10HP
A
(mm)
1265
2100
B
(mm)
835
870
Sling Bolt
Suspension Bracket