2 Control Functions
Control functions on the module
SMGB0120 rev.0 - 11/2017
32
Mode selection method
COOL
COOL/HEAT
Select "10 minutes"
Select "10 minutes"
2.1.15 Selection of enabling/disabling of alarm release by means of remote stop
The release of an alarm in case that the chiller unit has stopped due to an alarm is achieved by stop control (it is possible
to stop both from the stop button of the main unit or from remote stop control). But it is possible to configure this alarm
release to make it valid only from the stop button on the main unit (alarm cannot be released by remote stop control).
This function is valid for places where there is a remote device for automatic stop order when an alarm is emitted.
Select disable