2 Control Functions
Control functions on the module
SMGB0120 rev.0 - 11/2017
28
Pulse input type 1
a.
Signal aspect and basic sequence
For wiring
'&9
$
%
&
'
Terminal
board
Run/stop switch (to be
prepared locally)
Section arranged as a local work
Alarm output (DC24V, less than 0.8A)
Relay coil for DC24V, etc. (to be prepared
locally) (The relay coil is powered on in
case of alarm) Do not connect a LED or a
relay of internal diode type.
Time chart
Switch
Keep more than 5
minutes
More than
200ms
More than
200ms
ON
OFF
Run
Stop
Chiller
unit
?
N O T E
Pulse input indicates an ON input of the same switch when changing the status of the chiller unit, as shown in the diagram above.