2 Control Functions
Control functions on the module
SMGB0120 rev.0 - 11/2017
30
Pulse input type 2 (external DC24V source)
a.
Signal aspect and basic sequence
For wiring
5<
'&9
5<
5<
5<
Remove
(OFF)
(ON)
(ON) signal
(OFF) signal
Local works - parts to be arranged locally
(field supplied)
Time chart
5<
5<
5<
5<
ON
OFF
ON
ON
Run
Stop
Unit
More than 5 min
More than 200 ms
ON
OFF
Run
Stop
b.
Setting method
Since it applies remote control, it is not required to change any settings at the LCD screen.
?
N O T E
• Do not bundle the additional wiring together with other control circuits, and in particular with wiring for 230V or 400V.
• Put the additional wiring separately inside a metallic pipe, or use a shielded wire.