4 Troubleshooting
Troubleshooting by alarm code
SMGB0120 rev.0 - 11/2017
120
Alarm code
40-40
Transmission abnormality (Miswiring)
Alarm stop reason
The connection of wiring for transmission between modules (Transmission line between master and slaves) and the
transmission wiring for connection of group controller is mixed.
Retry indication
No retry
PCB monitoring position
PCBc (CPU PCB) CN2 (Transmission port between modules)
PCBc (CPU PCB) CN300 (Transmission port for group controller)
Connect transmission wiring
correctly
Check PCBc (CPU PCB)
No
Yes
The connection of
transmission wiring is
correct
Alarm code
6E-6E
Cold water suspension (Option)
Alarm stop reason
Suspension of water supply protection switch is activated.
PCB monitoring position
PCBc (CPU board) PCN10
Clogging of water
strainer
Check the water outage
protection switch
Check the pump flow
Check of wiring
Check the pump
Check of PCBc
(CPU PCB)
Yes
Yes
Yes
No
No
No
Hot-and-chilled water
is flowing with an amount
of flow higher than the usage
range
The connection and
insertion of connector PCN10
on PCBc (CPU PCB) are
correct
Remove the wiring
attached to connector PCN10
on PCBc (CPU PCB) and check
conductivity. Is there any
conductivity?