2 Control Functions
Control functions on the module
SMGB0120 rev.0 - 11/2017
10
2.1.2 Water temperature control
1
Automatic temperature adjustment
Compressor run/stop and capacity control are performed by detecting water temperature of the chiller unit with
thermistors.
Item
Model
Water Temp Set
ON/OFF Temperature Difference
Stop Temperature Range
Available range
(ºC)
Step (ºC)
Setting range
(ºC)
Step (ºC)
Setting range
(ºC)
Step (ºC)
Water-cooled
cooling only
4~30
0.5
0~4
Default: 2
1
0.5~2.0
Default: 1.0
0.5
?
N O T E
• Return temperature range indicates the amount of change in inlet water temperature of the chiller unit to determine thermo ON after
thermo OFF. (In the case of cooling: amount of temperature increase; in the case of heating: amount of temperature decrease)
• It is possible to change settings locally depending on usage purpose, but since the necessary volume of water will change, change the
settings only upon confirmation of the amount of the retained volume of water in the entire local system.
Output Cycle
Load up I
Output time
Load up II
Output time
Load down
Output time
Setting range
(Seconds)
10~120
(Default: 30)
10~120
(Default: 10)
2~120
(Default: 2)
2~120
(Default: 2)
Step
(Seconds)
10
1
1
1
Neutral Zone Range
Load up II range
Setting range (ºC)
1~5 (Default: 2)
1~3 (Default: 1)
Step (ºC)
1
1
?
N O T E
• Return temperature range indicates the amount of change in inlet water temperature of the chiller unit to determine thermo ON after
thermo OFF. (In the case of cooling: amount of temperature increase; in the case of heating: amount of temperature decrease).
• It is possible to change settings locally depending on usage purpose, but since the necessary volume of water will change, change the
settings only upon confirmation of the amount of the retained volume of water in the entire local system.