7
Technical data
General technical data
OZD Profi 12M ...
P11
P12
G11
G12
G12-EEC
G11-1300
G12-1300
G12-1300-EEC
Dimensions
W × H × D
See “Dimension drawings” on page 60.
Weight
approx. 19.75 oz (560 g)
Supply voltage
See “Requirements for connecting electrical wires” on page 6.
Nominal voltage DC
24 V
Voltage range DC incl.
maximum tolerances
18 V ... 32 V
Connection type
8-pin terminal block
Power loss buffer
> 10 ms at 20.4 V DC
Overload current protection
at input
Non-replaceable fuse
Back-up fuse for each
voltage input
Nominal rating:
Characteristic:
2 A
slow blow
Output voltage/current for
terminal resistors (Pin 6 D-
Sub socket)
5 V DC + 5%, -10%
Peak inrush current
< 4 A
Signal contact
See “Requirements for connecting electrical wires” on page 6.
Maximum Switching current 1 A
Maximum switching voltage 60 V DC
Maximum switching capacity max. 30 V DC, resistive load
Signal transmission
Transmission speed
9.6; 19.2; 45.45; 93.75; 187.5; 500 kBit/s 1.5; 3; 6; 12 Mbit/s
Setting transmission rate
automatic
Bit error rate
<10
-9
Signal processing time
(any input/output)
≤
6.5 t
Bit
Retimer
Input port 1 to 4
–
Signal distortion
–
Mean bit length
±30%
±0.12%
Output Port 1 to 4
Mean bit length
±0.01%
Electrical port
Isolation voltage
500 V
Input/output signal
RS 485 level
Summary of Contents for OZD Genius G12-1300
Page 67: ...Installation OZD Profi 12M Release 01 07 2017 67 ...
Page 68: ...68 Installation OZD Profi 12M Release 01 07 2017 ...
Page 69: ...Installation OZD Profi 12M Release 01 07 2017 69 ...
Page 70: ...70 Installation OZD Profi 12M Release 01 07 2017 ...
Page 71: ...Installation OZD Profi 12M Release 01 07 2017 71 ...
Page 72: ......