Installation OZD Profi 12M ...
Release 01 07/2017
59
EMC and immunity
Power consumption/power output
Transmission distance:
Fiber 10/125
-
15000 m
Fiber 50/125 (default)
-
3000 m
10000 m
Fiber 62.5/125 (default)
-
3000 m
10000 m
Fiber 200/230/125 (default)
400 m
-
-
Fiber 200/230/125 (reduced)
-
800 m (12 MBit/s)
1000 m
(<12 MBit/s)
-
Fiber 980/1000 (default)
80 m
-
-
Fiber 980/1000 (reduced)
57 m
-
-
a. The specified transmission distance must not be exceeded regardless of the maximum
allowed attenuation line.
EMC interference emission
Radiated emission
EN 55022
Class A
EN 55032
Class A
FCC 47 CFR Part 15
Class A
EMC interference immunity
Electrostatic discharge
EN 61000-4-2
IEEE C37.90.3
Contact discharge
± 4 kV
EN 61000-4-2
IEEE C37.90.3
Air discharge
± 8 kV
Electromagnetic field
EN 61000-4-3
80 MHz ... 1000 MHz
10 V/m
1400 MHz ... 2000 MHz
Fast transients (burst)
EN 61000-4-4
IEEE C37.90.1
DC supply connection
± 2 kV
EN 61000-4-4
IEEE C37.90.1
Data line
± 1 kV
Voltage surges - data line
EN 61000-4-5
line/ground
± 1 kV
Conducted disturbances
EN 61000-4-6
150 kHz ... 80 MHz
10 V
Device name
Maximum power consumption Maximum power output
OZD Profi 12M ...
3.9 W (1 electrical port)
13.3 BTU (IT)/h
4.7 W (2 electrical ports)
16 BTU (IT)/h
Transmission distance
a
P
G
G-1300
Summary of Contents for OZD Genius G12-1300
Page 67: ...Installation OZD Profi 12M Release 01 07 2017 67 ...
Page 68: ...68 Installation OZD Profi 12M Release 01 07 2017 ...
Page 69: ...Installation OZD Profi 12M Release 01 07 2017 69 ...
Page 70: ...70 Installation OZD Profi 12M Release 01 07 2017 ...
Page 71: ...Installation OZD Profi 12M Release 01 07 2017 71 ...
Page 72: ......