54
Installation OZD Profi 12M ...
Release 01 07/2017
5
Configuration
During configuration, the PROFIBUS network parameter "Slot time" must be
adapted to the network coverage, network topology and the data rate due to
frame delays caused by lines and network components, as well as by
monitoring mechanisms in the network components.
Configuration of redundant optical rings
The following configuration conditions must be fulfilled in the redundant
optical ring
See “Redundant ring” on page 30.
– (1) Configuration of a non-existent bus subscriber
– (2) Increasing the retry value to at least 3
– (3) Checking and adjusting the slot time
Use the user-specific profile of the configuration tool to set the parameters
under (2) and (3).
Calculate the slot time with the following equation:
Slot time = a + (b × Length
OF
) + (c × Number
OZD
)
Slot time
is the monitoring period in bit times.
Length
OF
is the sum of all the optical fiber lines (segment lengths) in
the network.
Number
OZD
is the number of OZD Profi 12M ... in the network.
Data rate
a
b
c
12 Mbit/s
a
a. Use the values from
table 9
if the calculated slot time is smaller than the
minimum slot time indicated in the table.
1651
240
28
6 Mbit/s
a
951
120
24
3 Mbit/s
a
551
60
24
1.5 Mbit/s
a
351
30
24
500 kBit/s
251
10
24
187.5 kBit/s
171
3.75
24
93.75 kBit/s
171
1.875
24
45.45 kBit/s
851
0.909
24
19.2 kBit/s
171
0.384
24
9.6 kBit/s
171
0.192
24
Table 7:
Constants for calculating the slot time at DP standard (redundant optical
ring).
Summary of Contents for OZD Genius G12-1300
Page 67: ...Installation OZD Profi 12M Release 01 07 2017 67 ...
Page 68: ...68 Installation OZD Profi 12M Release 01 07 2017 ...
Page 69: ...Installation OZD Profi 12M Release 01 07 2017 69 ...
Page 70: ...70 Installation OZD Profi 12M Release 01 07 2017 ...
Page 71: ...Installation OZD Profi 12M Release 01 07 2017 71 ...
Page 72: ......