Installation OZD Profi 12M ...
Release 01 07/2017
2
Network Topologies
The following network topologies can be realized with the OZD Profi 12M ...:
Point-to-point connections
Line topologies
Star topologies
Redundant optical rings
Note:
Single terminals or entire PROFIBUS segments with max. 31 subscribers
can be connected to the electrical interface of the OZD Profi 12M ...
In areas with a high EMC incidence, only lay optical fiber lines in order to
exclude the possibility of EMC affecting the whole network.
Optically only OZD Profi 12M ... of the same type can be connected
together: OZD Profi 12M P11 with … P12, OZD Profi 12M G11 with
…G12 and …G12 EEC, OZD Profi 12M G11-1300 with … G12-1300 and
…G12-1300 EEC.
Optical ports which are connected by optical fiber must be set to the same
operating mode.
Junctions between different OZD Profi 12M ... types are only possible via
the RS 485 interface.
OZD Profi 12M G12 (-1300) EEC can be used everywhere in those
network topologies described below in which a OZD Profi 12M G12(-
1300) can also be used.