56
Function Specifications
Comparator
• Voc
Threshold value can be set in 1 V increments from
0 V to 20 V for the absolute value of Voc diff.
Voc diff ≥ Threshold value: FAIL
Voc diff < Threshold value: PASS
• BPD TEST mode
Threshold value can be set in 0.5
Ω
increments
from 0
Ω
to 15
Ω
for R
BPR
.
R
BPR
≥ Threshold value: FAIL
R
BPR
< Threshold value, and
Detected peak currentd < Measured short-circuit
c additional current × 0.8: FAIL
Detected peak current ≥ Measured short-circuit
c additional current × 0.8: PASS
Judgment is available only when the auto-hold is
enabled.