8
TECHNICAL DATA
128
Senator S24S
01/2019 - Senator S24S Radar Manual v1.00 en
Process connections
Thread
G 1 A...1
½
A (ISO 228); 1...1
½
NPT (ASME B1.20.1)
Flange version
Flange version
Flange version
Flange version
EN 1092-1
Low-pressure flanges: DN80...200 in PN01;
Standard flanges: DN80...200 in PN10, PN16 and PN40 (Type B1); others on request
Optional flange facing for standard flanges: Type A
ASME B16.5
Low-pressure flanges: 3
¨
...8
¨
in 150 lb (max. 15 psig);
Standard flanges: 3
¨…
8
¨
in 150 lb RF and 300 lb RF; others on request
Optional flange facing for standard flanges: FF (Flat Face)
JIS B2220
80
…
200A in 10K RF; others on request
Other
Others on request
Electrical connections
Power supply
Terminals output
Terminals output
Terminals output
Terminals output
–
Non-Ex / Ex i:
Non-Ex / Ex i:
Non-Ex / Ex i:
Non-Ex / Ex i:
12
…
30 V DC; min./max. value for an output of 21.5 mA at the terminals
Terminals output
Terminals output
Terminals output
Terminals output
–
Ex d:
Ex d:
Ex d:
Ex d:
16
…
36 V DC; min./max. value for an output of 21.5 mA at the terminals
Maximum current
21.5 mA
Current output load
Non-Ex / Ex i:
Non-Ex / Ex i:
Non-Ex / Ex i:
Non-Ex / Ex i: R
L
[
Ω
]
≤
((U
ext
-12 V)/21.5 mA). For more data, refer to
Minimum
power supply voltage
on page 133.
Ex d:
Ex d:
Ex d:
Ex d: R
L
[
Ω
]
≤
((U
ext
-16 V)/21.5 mA). For more data, refer to
Minimum power supply
voltage
on page 133.
Cable entry
Standard: M20×1.5; Options:
½
NPT; 4-pin male M12 connector
Cable gland
Standard: none
Options: M20×1.5 (cable diameter: 7
…
12 mm / 0.28
…
0.47
¨
); others are available on
request
Cable entry capacity (terminal)
0.5
…
3.31 mm
²
(AWG 20...12)
Input and output
Current output
Current output
Current output
Current output
Output signal
Standard: 4
…
20 mA
Options: 3.8
…
20.5 mA acc. to NAMUR NE 43; 4
…
20 mA (reversed); 3.8
…
20.5 mA
(reversed) acc. to NAMUR NE 43
Output type
Passive
Resolution
±
5
µ
A
Temperature drift
Typically 50 ppm/K
Error signal
High: 21.5 mA; Low: 3.5 mA acc. to NAMUR NE 43
HART
HART
HART
HART
®
Description
Digital signal transmitted with the current output signal (HART
®
protocol)
2
Version
7.4
Load
≥
250
Ω
Digital temperature drift
Max.
±
15 mm / 0.6
¨
for the full temperature range
Multi-drop operation
Yes. Current output = 4 mA. Enter Program mode to change the polling address
(1...63).
Available drivers
FC475, AMS, PDM, FDT/DTM
www.hawkmeasurement.com
Summary of Contents for Senator S24S
Page 173: ...NOTES 11 173 Senator S24S 01 2019 Senator S24S Radar Manual v1 00 en www hawkmeasurement com...
Page 174: ...11 NOTES 174 Senator S24S 01 2019 Senator S24S Radar Manual v1 00 en www hawkmeasurement com...
Page 175: ...NOTES 11 175 Senator S24S 01 2019 Senator S24S Radar Manual v1 00 en www hawkmeasurement com...