OPERATION
6
111
Senator S24S
01/2019 - Senator S24S Radar Manual v1.00 en
6.5 Status messages and diagnostic data
Device status and error messages are shown on a device status page in Normal mode and in
menu item "C7.3.1 Messages View" in Program mode. Messages shown agree with NAMUR
Guidelines NE 107. The error messages for the device are divided into status groups, each with
one status signal. There are 16 status groups with fixed status signals and 8 groups with status
signals that can be changed. The status groups are also divided into 4 groups: Sensor,
Electronics, Configuration and Process.
Each status message (or status signal) has a special symbol which agrees with the NAMUR
Guidelines. This symbol is shown with the message.
Status messages (NAMUR NE 107)
Normal mode: device status symbol
If the device status changes, the device shows a status symbol in the top left corner of the display
screen in Normal mode:
The status group name and the status signal (F/S/M/C) are shown. For more data, refer to the
table that follows.
Symbol
Letter
Message
Description and effect
F
F
F
F
Failure
No measurement is possible.
S
Out of specification
Measurements are available but they are
not sufficiently accurate. Do a check.
M
Maintenance required
Measurements continue to be accurate but
this could change after a short time.
C
Function check
A test function is on. The value shown does
not agree with the correct measured value.
I
Information
This status message does not have an effect
on device measurements.
Figure 6-11: Device status: Normal mode
1
Device status symbol (NAMUR NE 107)
www.hawkmeasurement.com