6
OPERATION
102
Senator S24S
01/2019 - Senator S24S Radar Manual v1.00 en
6.4.3 HART
®
network configuration
The device uses HART
®
communication to send information to HART
®
-compatible equipment. It
can operate in either point-to-point or multi-drop mode. The device will communicate in multi-
drop mode if you change the polling address.
How to change from point-to-point to multi-drop mode
•
Enter Program mode.
•
Push 2 × [
], [>>>>], 3 × [
], 2 × [>>>>], [
] and 2 × [>>>>] to go to menu item C5.1.2.1 Polling Address.
•
Enter the password used at this time for the "Expert" access level. If it is the default password,
enter "0058". Push [
^
^
^
^
] to confirm.
•
Enter a value between 001 and 063 and push [
^
^
^
^
] to confirm.
•
Push [
^
^
^
^
] again and again to go back to the Save Configuration?
Save Configuration?
Save Configuration?
Save Configuration? screen.
•
Push [
] or [
] to set the screen to "Yes" and push [
^
^
^
^
].
i
The output is set to multi-drop mode. The current output is set to 4 mA. This value does not
change in multi-drop mode.
How to change from multi-drop to point-to-point mode
•
Enter Program mode.
•
Push 2 × [
], [>>>>], 3 × [
], 2 × [>>>>], [
] and 2 × [>>>>] to go to menu item C5.1.2.1 Polling Address.
•
Enter the password used at this time for the "Expert" access level. If it is the default password,
enter "0058". Push [
^
^
^
^
] to confirm.
•
Enter the value 000 and push [
^
^
^
^
] to confirm.
•
Push [
^
^
^
^
] again and again to go back to the Save Configuration?
Save Configuration?
Save Configuration?
Save Configuration? screen.
•
[
] or [
] to change the parameter
("Disable" or "Enable").
•
[
^
^
^
^
] to confirm.
Empty Spectrum Enable. If you set the
menu item to "Enable", the device will use
the empty spectrum recording data. If you
set the menu item to "Disable", the device
will not use the empty recording data at
this time.
•
4 × [
^
^
^
^
] to confirm.
•
[
] or [
] for the selection of the
save option (Yes, No or Back).
•
[
^
^
^
^
] to confirm.
Save Configuration?
Save Configuration?
Save Configuration?
Save Configuration? screen.
Set to "Yes" to save and use the settings
and data and go back to Normal mode. Set
to "No" to cancel the changes to the device
settings and go back to Normal mode. Set
to "Back" to stay in Program mode.
For more data, refer to Networks on page 52
.
Screen
Steps
Description
CAUTION!
Make sure that the address for this device is different from others in the multi-drop network.
Make sure that menu item C5.1.1 Current Loop Mode is set to "On".
www.hawkmeasurement.com
Summary of Contents for Senator S24S
Page 173: ...NOTES 11 173 Senator S24S 01 2019 Senator S24S Radar Manual v1 00 en www hawkmeasurement com...
Page 174: ...11 NOTES 174 Senator S24S 01 2019 Senator S24S Radar Manual v1 00 en www hawkmeasurement com...
Page 175: ...NOTES 11 175 Senator S24S 01 2019 Senator S24S Radar Manual v1 00 en www hawkmeasurement com...