18. Always use oxygen compatible leak test solution on oxygen or nitrous oxide service equipment. 

2. Introduction

  All Harris Products Group Gas Distribution systems are cleaned, tested and prepared for the indicated gas service and are built following National Fire Protection Association (NFPA) 

and Compressed Gas Association (CGA) guidelines.  The 220 Series Switchover Manifold consists of a control hub (Box) and two supply bank headers or hoses, one primary and one 
reserve, to provide an uninterrupted supply of gas for the specific application. The control box is designed and built with features providing automatic switchover from the depleted 
primary supply bank to the reserve supply bank.  Pressure gauges, optional alarm signal connections and lights show system status and alert the need to replace depleted cylinders. 

Features of the automatic system include an adjustable line regulator, hoses with check valves, wall-mounted header bar assemblies and wall mounting brackets. 
 

3. Description

  The Model 220 Series Switchover Manifolds are designed to provide a continuous supply of gas. The system automatically changes from a depleted bank of cylinders in service to 

the full reserve bank without an interruption of gas supply. A simple rotation of the primary bank selector knob resets the unit once the depleted bank of cylinders has been replaced. 
The standard outlet regulator maintains a constant line pressure, even during the switchover process.

4. General Instructions

  Manifolds should be installed in accordance with guidelines stated by the National Fire Protection Association, the Compressed Gas Association, OSHA and all applicable local codes. 

The manifolds should not be placed in a location where the temperature will exceed 120°F (49°C) or fall below –20°F (-29°C) for sustained periods of time.  

A manifold placed 

outside in an open location should be protected against rain and excessive moisture.  During winter, protect the manifold from ice and snow.  The manifold should 

be located in a clean, well-ventilated area which is free of oil and combustible materials.

Leave all protective covers in place until their removal is required for installation. This precaution will keep moisture and debris from the piping interior, avoiding operational problems.

All safety relief valves should be piped/vented to an outside location away from personnel.  Failure to properly pipe away the external manifold relief valve can create hazardous 
conditions.  Flammable, oxidizing and asphyxiant gases in the general vicinity of personnel can result in extremely hazardous conditions.  Any failure of internal pressure reducing valves, 
seats or seals can cause excess pressure to build up and release dangerous gases into the surrounding environment.

5. Design Specifications

 
 

Maximum Inlet Pressure 

220 – High Pressure: 3000 psi 

 

 

220 – Acetylene: 400 psi 

 

 

220 – LP Gases: 400 psi 

 

Operating Temperature 

-20 degrees F to +120 degrees  F

 

Pressure Gauge Size 

 2” Dial 

 

Inlet Connection 

½” FNPT Port 

 

Outlet Connection 

 ½” FNPT Port

 

Alarm 

Integral for Non-Flammable Gas Systems, Optional Remote Alarm Available For All Systems

 

Header 

½” Nominal Pipe Size 

 

Power Requirements 

Manifold Box: 120 VAC, 1.25 Amp. For Oxy/Inert Systems Power is not required for flammable gas systems

  

 

Heaters for 220HL, 220HLHP: 120 VAC, (2) heaters @ 200W, 4A Max

 

Flexible Hose Length 

24” or 36” unless otherwise specified

  

6. Standard Factory Pressure Settings

  

Inlet Pressure Gauge 

220, 220HL, 220HP  – High Pressure: 0-4000 psi 

  

 

220 – Acetylene: 0-400 psi 

  

 

220 – LP Gases: 0-400 psi 

 

Outlet Pressure Gauge  

220, 220HL  – High Pressure:    0-200 psi, 220HP: 400 psi

  

 

220 – Acetylene: 0-30 psi 

  

 

220 – LP Gases: 0-100 psi 

 

Outlet Pressure Range 

220, 220HL – High Pressure:  5-125 psi, 220HP: 200 psi

  

 

220 – Acetylene: 0-15 psi

  

 

220 – LP Gases: 0-30 psi

 

Switchover Pressure 

220, 220HL – High Pressure: 170 psi, 220HP: 230 psi

  

 

220 – Acetylene: 65 psi

  

 

220 – LP Gases: 65 psi

 

Alarm Set Point  

220, 220HL – High Pressure: 200 psi, 220HP: 240 psi  

  

 

220 – Acetylene: 75 psi 

  

 

220 – LP Gases: 75 psi

 

Relief Valve Set Point 

220, 220HL – 250 psi

 

 

220 HP220HLHP – 500 psi

  

220 LPGases – 100 psi

  

220 Acetylene – 21 psi

THE HARRIS PRODUCTS GROUP

www.harrisproductsgroup.com

1.800.241.0804

Summary of Contents for 220 Series

Page 1: ...lable in close proximity 7 Many gases can cause asphyxiation by displacing oxygen in the atmosphere Make certain the area where these manifolds are operated is well ventilated 8 Do not release asphyxi...

Page 2: ...snow The manifold should be located in a clean well ventilated area which is free of oil and combustible materials Leave all protective covers in place until their removal is required for installatio...

Page 3: ...may be used The outlet port connection on the control box is FNPT Note Acetylene systems are supplied with a pipeline protection device required by NFPA It is intended that this device be installed di...

Page 4: ...off valves 4 Turn the selector knob on the control box to the primary side right or left 5 S L O W L Y open the first cylinder valve on the primary side Warning It is important that all cylinder valve...

Page 5: ...ary Preset Outlet Inlet Delivery Pressure Green Red Heater Power Number Box P N Regulator Regulator Regulator Gauge Gauge Switch Light Light Assembly Supply 220 Oxy Inlet 4301529 3001570 3001602 30016...

Page 6: ...de seguridad que deben tenerse en cuenta cuando se manejan gases comprimidos Si no est seguro de comprender por completo las precauciones de seguridad para manejar gases comprimidos comun quese con H...

Page 7: ...nsiste de un cubo de control caja y dos cabezales o mangueras de banco de suministro uno principal y otro de reserva a fines de proporcionar un suministro ininterrumpido de gas para la aplicaci n espe...

Page 8: ...ualquier requisito el ctrico 8 Instrucciones de instalaci n NOTA Puede ver un video detallado sobre una t pica instalaci n en http bit ly S4BUgV Los colectores de la serie 220 pueden utilizarse con do...

Page 9: ...control Esto garantizar que el suministro de gas del sistema del colector pueda cerrarse r pidamente en una situaci n de emergencia 5 Si el sistema solo tiene un cilindro en cada lado sin una barra d...

Page 10: ...Allen 5 32 in Gire el tornillo de ajuste hacia la derecha hasta que se lea la presi n deseada en el man metro de presi n de suministro Puede tomar algunos segundos para que la presi n se iguale en la...

Page 11: ...electricidad o el suministro el ctrico es defectuoso Verifique la entrada de voltaje en el suministro el ctrico debe ser de 115 VCA Verifique la salida de voltaje del suministro el ctrico debe ser de...

Page 12: ...lles et de collecteurs de m me que le robinet principal doivent toujours tre ouverts tr s l e n t e m e n t La chaleur due la recompression risque d enflammer les mat riaux combustibles 13 Les flexibl...

Page 13: ...psi 220 Gaz de p trole liqu fi s GPL 0 100 psi Plage de pression de sortie 220 220HL Haute pression 5 125 psi 220HP 200 psi 220 Ac tyl ne 0 15 psi 220 Gaz de p trole liqu fi s GPL 0 30 psi Pression de...

Page 14: ...positif est pr vu pour tre install directement sur le raccord de sortie du boitier de contr le Toutefois il peut tre install plus en aval si n cessaire Il doit tre install entre le boitier du collecte...

Page 15: ...uvrez L E N T E M E N T le robinet d arr t principal du c t de la source principale et v rifiez la pr sence de fuites au niveau du raccord entre la barre de collecteur et le boitier de contr le l aide...

Page 16: ...niveau de la tuyauterie en aval V rifiez qu aucun raccord ou joint ne pr sente de fuites resserrez r parez ou remplacez les tuyaux ou les raccords Fuite au niveau du robinet de la bouteille V rifiez q...

Reviews: