FIRE SUPPRESSION SYSTEM FOR 

PROFESSIONAL KITCHENS

 

DIAS

 

INSTRUCTIONS MANUAL

 

Summary of Contents for DIAS

Page 1: ...FIRE SUPPRESSION SYSTEM FOR PROFESSIONAL KITCHENS DIAS INSTRUCTIONS MANUAL ...

Page 2: ...MVK MAN DIAS REV 4 17 09 2018 1 ...

Page 3: ...f the Wet Chemical Agent through Stainless steel Tube Network and Discharge through special type Nozzles In Manual Operation the system can be activated by Electrical Means by a an Extinguish Button that is built in to the Control Panel or b an System Activation Call Point that must be installed near to the Kitchen Exit or by Mechanical Means by a a Metal Wire Mechanism that must be installed near...

Page 4: ...scharge of the Extinguishing Agent is realized simultaneously from all the Nozzles thus preventing the fire transmission from area to area Note Fire Detection Suppression Control Panel has a built in Autonomy Battery lasting a 90 minutes fully operating and b 72 hours in idle position hence ensuring Automatic System activation in case of electric power shut down in the Kitchen During the time dela...

Page 5: ...work 5 1 MBK12 WIRE 138 Linear Heat Detection Cable 138 C 5 2 MBK12 WIRE 180 Linear Heat Detection Cable 180 C 5 3 MBK12 WIRE 250 Linear Heat Detection Cable 250 C 6 MBK12 CLEMA Porcelain Splice Connectors used for Linear Heat Detection Cable Connections 7 MBK12 DEMATIKO Stainless Steel Straps used for Linear Heat Detection Cable Support 8 MBK12 FIRETAPE Fire Tape used for Linear Heat Detection Ca...

Page 6: ...r 1pcs A3 1 5 Air Duct 61cm Diam 190cm Perim 1pcs A9 2 Exhaust Hood 305cm Length 1pcs A2 1 Deep Fryer 48 x 64 cm 1pcs A9 2 Cooking Plate 76 x 122 cm 1pcs A8 2 Cooking Plate 76 x 107 cm 1pcs A9 2 Cooking Plate 76 x 91 cm 1pcs A2 1 Electrical Oven 31 x 61 cm 1pcs A2 1 Electrical Oven 61 x 61 cm 1pcs A8 2 Oven 72 x 72 cm 2pcs A4 1 5 Electrical Grill 52 x 61 cm 1pcs A2 1 Propane Gas Grill 52 x 61 cm 1...

Page 7: ... Duct 81cm dia 2pcs A3 3 Hood 305cm length 1pc A2 1 STEP 3 Then calculate the Sum of Flow Units based on the above table step 2 and the total A8 ejector pieces step 1 Flow Unit Sum 5pcs A8 x 2 3 1 14 Flow Units STEP 4 To find the amount of Extinguishing Material divide the sum of the Flow Units by the Fixed Coefficient of 0 8 that is Amount of Extinguishing Material 14 0 8 17 5ltr STEP 5 Select th...

Page 8: ...e small hole from where the agent is been discharged Note 3 Stainless Steel Tubes and Components required for the construction of the System s Pipe Network are not traded by MOBIAK and must be supplied from local market LINEAR HEAT DETECTION CABLE Linear Heat Detection Cable is a fixed temperature sensor of activation temperatures 138 C 180 C or 250 C The selection of Activation Temperature of the...

Page 9: ...screw Step 3 Secure Linear Heat Detector by tightening the connector screws Plastic screw turrets may be trimmed with snips or utility knife for easier taping Step 4 Using 10 1cm 12 7cm of Electrical Tape wrap the splice Stretch and overlap each wrap of tape The installer must ensure proper connections and conductors proper insulation by special Fire Tape in case that the conductor is not properly...

Page 10: ...ireproof Blanket FIRE DETECTION SUPPRESSION PANEL MOB 2001 is a Fire Detection Suppression Panel that incorporates Siren with Beacon Extinguish Button Extinguish Cancel Switch built in Battery Electrical Relay for shut down the Power Supply of Electrical Devices Duct Fans as well as the Gas Valve The connections on the Panel are easy fast and take place outside the Panel factory made external wiri...

Page 11: ...lve Rod Metal Wire Mechanism System Activation Call Point which should be always in reach with ease and without any obstacles in front Visual check of Linear Heat Detection Cable for defects Visual check of the Fire Detection Suppression Panel operational status indication LED s Visual check of the Fire Extinguisher Pressure Gauge so that to secure correct pressure indication which must always be ...

Page 12: ...able cloth use of clean water so that to remove grease or fat Replacement of the Fire Tape used for insulating the connections of the Linear Heat Detection Cable on the Connections Operational Check Maintenance of System s Fire Detection Suppression Panel according to Manufacturer s Manual Replacement of Fire Detection Suppression Panel battery every five 5 years according to Manufacturer s Manual...

Page 13: ...ntenance as well as the full name of the technician who executed the maintenance SYSTEM REFILLING The local application Fire Extinguisher of the Fire Suppression System should always be refilled exclusively with Wet Chemical Agent approved by MOBIAK in any of the following cases Immediately after five 5 years from the production date of the Fire Extinguisher according to European Regulation guidel...

Page 14: ...MVK MAN DIAS REV 4 17 09 2018 13 INSPECTION FORM Α Α DATE TECHNICIAN FULL NAME DESCRIPTION OF SERVICES SIGNATURE 01 02 03 04 05 06 07 08 09 10 11 12 ...

Page 15: ...MVK MAN DIAS REV 4 17 09 2018 14 MAINTENANCE FORM Α Α DATE TECHNICIAN FULL NAME DESCRIPTION OF SERVICES SIGNATURE 01 02 03 04 05 06 07 08 09 10 11 12 ...