No. C4b End AT loading when temperature (parameter C4) has been reached on
the selected sensor
Only displayed when installer setting
C2
is set with
2, 3
or
5 sensors
No. C4c AT minimum temperature
Lower accumulator limit temperature
When the accumulator temp is below the set value (accumulator sensor top),
AT loading starts
No. C4d Accumulator power reduction
When the preset accumulator filling level is reached, the boiler's power is
reduced.
No. C4e Accumulator error recognition
A warning is issued when the mixer is completely open for the preset time
and the temperature at the bottom accumulator sensor is 11 °C below that of
the return sensor.
No. C4 Accumulator
Setting the time for accumulator forced loading
Displays only if parameter
C2
is set to
AT with 2 sensors
or
AT with 3 sen
-
sors
Accumulator forced loading at the set time and activated set temperature
E.g. for peak loads in the morning (e.g. 4:00 - 10:00)
.
No. C5a Accumulator forced loading
No accumulator forced loading when the set outside temperature is exceeded
.
No. C6 External heat circuit
Adjusting the boiler set temperature for an activated external heat circuit
If the value is changed and parameter
C7
is set to
external pump
, then
adjust the service-parameter
L5
= 50 °C as well
L5 ca. 5 - 10 [°C] less than
C6a
No.C7 Function of terminal 83
Set the function of the output at terminal 83 on the main board.
• Fault lamp
Lights up for all faults
• Pump external heat circuit
Boiler is heated to the temperature set in parameter
C6
External heat circuit pump is switched on at release temperature (service
setting
L5
)
• District line pump
District line runs when a heating circuit or HWT pump parametrised for
district line
is switched on
No. C8 External heat circuit and district heat pump
District heating pump runs if one of the referred pumps run
No. C9 External heat
• non-existent
• Oil/gas boiler
• Solid fuel boiler
HARGASSNER
Mo,25.11.18 08:19
Acc. Bottom
ACC Top
No. C4b End accumulator loading (due
to domestic hot water production)
Sensor: (temperature C4)
AT center
HARGASSNER
Mo,25.11.18 08:19
Accumulator min. temp. (Accumulator top)
Default: 0 °C
No. C4c Accumulator
0 °C
HARGASSNER
Mo,25.11.18 08:19
Power reduction at fill level over
Default: 85%
No. C4d accumulator
85 %
HARGASSNER
Mo,25.11.18 08:19
Error recognition acc. sensor
bottom after (0 = deactivated)
Default: 30 min.
No. C4e accumulator
30 Min
HARGASSNER
Mo,25.11.18 08:19
No. C5 Forced acc. loading Week clock
ON
Off
Off
ON
M Tu W Th F Sa Su
--:--
i
--:--
i
--:--
i
--:--
i
HARGASSNER
Mo,25.11.18 08:19
No forced accumulator loading at
outside temperature over
Default: 0 °C
No. C5a Accumulator
0 °C
HARGASSNER
Mo,25.11.18 08:19
External heating setpoint temp.
Default: 69 °C
No. C6 External heat circuit
69 °C
HARGASSNER
Mo,25.11.18 08:19
No.C7 Function of terminal 83
Fault lamp
External pump
Distr. heat pump 1
HARGASSNER
Mo,25.11.18 08:19
No. C8 External heat circuit and district heat
pump
no district heating
with district line 1
Controlled district line
HARGASSNER
Mo,25.11.18 08:19
No. C9 External heat
non-existent
Oil / Gas
Solid fuel