Technical Data
7
Flue pipe - chimney connections
8
Electrical supply
See according to enclosed electrical manual
• The electrical connection may only be established by a licensed and authorised
electrician and must be done in accordance with the enclosed electrical manual.
• Attach a lockable main power switch outside of the boiler room (depending on
building regulations).
• Max. prefuse
13 A
(C characteristic)
• It is absolutely imperative that the intrinsically safe cables are
permanently installed
• Use suitable mechanical components
• in-phase connection
L
and
N
(see electrical manual)
• Connect potential equalisation
• Use highly flexible cables (e.g.
H05VV-F
)
Description
Unit
Classic 12
Classic 14
Classic 15
Classic 22
Nominal heating output
KW
12.0
14.9
15.0
22.0
Flue gas temperature
°C
150
150
150
150
CO
2
%
14
Mass volume
kg/Sec
0.0071
0.0082
0.0088
0.0129
Necessary pressure
Pa
2
Flue draft max. limit
Pa
10
Diameter of flue pipe connection
mm
130
Water resistance dT 10°
mbar
6.2
7.2
7.7
18.3
Water resistance dT 20°
mbar
2.0
2.3
2.5
3.8
Electrical energy
Characteristics
Unit
Voltage
230
V ± 5 %
Frequency
50
Hz ± 5 %
Fuse
13
A
Power consumption
47
W