9.5
Parameter list Customer settings
9.5.1 Extension module 0
9.5.2 Heat circuit board HC A
9.5.3 Extension module HKM 1
Menu
Description
Factory:
Modbus ad
-
dress
1
HWT 1 day clock Mon - Sun
ON 17:00 OFF 20:00
2001
1a-g
HWT 1 weekly Mo/Tu/We/Th/Fr/Sa/Su
ON 17:00 OFF 20:00
2005 - 2035
(intervals of 5)
2
HWT 1 Set temperature
60°C
2040
2a
Circulation pump HWT 1
ON 06:00 11:00 16:00
OFF 08:00 13:00 20:00
2041
3
Heat circuit 1 day clock Mon - Sun
ON 06:00 15:00
OFF 09:00 22:00
2050
3a-g
Heating circuit 1 weekly Mo/Tu/We/Th/Fr/Sa/Su
ON 06:00 15:00
OFF 09:00 22:00
2055 - 2085
(intervals of 5)
4
Heat circuit 1 Day-room temperature
20.0°C
2090
5
Heat circuit 1 Reduction temperature
16.0°C
2092
6
Heat circuit 2 day clock Mon - Sun
ON 06:00 15:00
OFF 09:00 22:00
2094
6a-g
Heating circuit 2 weekly Mo/Tu/We/Th/Fr/Sa/Su
ON 06:00 15:00
OFF 09:00 22:00
2098 - 2128
(intervals of 5)
7
Heat circuit 2 Day-room temperature
20.0°C
2133
8
Heat circuit 2 Reduction temperature
16.0°C
2135
Menu
Description
Factory:
Modbus ad
-
dress
HP1
HWT A daily Mon-Sun
ON 17:00 OFF 20:00
2140
HP 1a-g HWT A weekly Mo/Tu/We/Th/Fr/Sa/Su
ON 17:00 OFF 20:00
2145 - 2175
HP 2
HWT A Set temperature
60 °C
2180
HP 2a
Circulation pump HWT A
ON 06:00 11:00
OFF 08:00 13:00
2185
HP 3
Heating circuit A daily Mon-Sun
ON 06:00 15:00
OFF 09:00 22:00
2190
HP 3a-g Heating circuit A weekly Mo/Tu/We/Th/Fr/Sa/Su ON 06:00 15:00
OFF 09:00 22:00
2195 - 2225
HP 4
Heat circuit A Day-room temperature
20.0 °C
2230
HP 5
Heat circuit A reduction-room temperature
16.0 °C
2237
Menu
Description
Factory:
Modbus ad
-
dress
H 1
HWT 2 day clock Mon - Sun
ON 17:00 OFF 20:00
2240
H 1a-g
HWT 2 weekly Mo/Tu/We/Th/Fr/Sa/Su
ON 17:00 OFF 20:00
2245 - 2275
H 2
HWT 2 Set temperature
60°C
2280
H 2a
Circulation pump HWS 2
ON 06:00 11:00
OFF 08:00 13:00
2281
H 3
HWT 3 Day clock Mo-Su
ON 06:00 15:00
OFF 09:00 22:00
2286
H 3a-g
Heating circuit 3 weekly Mo/Tu/We/Th/Fr/Sa/Su
ON 17:00 OFF 20:00
2291 - 2321
H 4
Heat circuit 3 Day-room temperature
20°
2326
H 5
Heat circuit 3 Reduction temperature
16°
2328
H 6
HWT 4 Day clock Mo-Su
ON 06:00 15:00
OFF 22:00 09:00
2330
H 6a-g
Heating circuit 4 weekly Mo/Tu/We/Th/Fr/Sa/Su
ON 17:00 OFF 20:00
2335 - 2365