STRATTON MK3 - Installation, Use and Maintenance
Boiler only
1 non-regulated circuit with sliding flow
Diagrams
MK3-20,
page 1 / 4
A. HYDRAULIC DIAGRAM
Figure 28 - MK3-20 diagram
The boiler operates in variable flow temperature according to the outdoor temperature measured by the
exterior sensor QAC 34.
The heating water law is programmed on the NAVISTEM B3100, with or without a low temperature limit
and with a weekly programme.
The heating pump must be able to operate at a constant speed to ensure the minimum flow rate that is
required by the generator.
If the installation is equipped with thermostatic taps on the emitters, the bypass between the outward and
return lines of the network is essential. It is equipped with a differential valve that allows for the free flow of
the heating pump when the thermostatic taps close.
Minimum flow
Model (kW)
40
60
70
80
100
120
150
Minimum flow (l/min)
9,5
19,2
19,2
38,3
38,3
50,0
57,3
Summary of Contents for STRATTON MK3 Series
Page 2: ......
Page 13: ...06 02 2023 13 154 STRATTON MK3 Installation Use and Maintenance...
Page 44: ...44 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C Figure 19 Wiring diagram...
Page 45: ...06 02 2023 45 154 STRATTON MK3 Installation Use and Maintenance...
Page 149: ...06 02 2023 149 154 STRATTON MK3 Installation Use and Maintenance...
Page 150: ...150 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C...
Page 151: ...06 02 2023 151 154 STRATTON MK3 Installation Use and Maintenance...
Page 152: ...152 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C...
Page 153: ...06 02 2023 153 154 STRATTON MK3 Installation Use and Maintenance...