136 / 154
STRATTON MK3 - Installation, Use and Maintenance
00U07428680-C
For
VFC
signals
Contacts on X1 L (1) and QX21 (7) can be used for the following:
Boiler flame on/Boiler demand (closed contact)
Contacts on X1 L (1) and QX22 (5) can be used for the following:
Fault errors (closed contact)
E133 flame failure
E110 temperature high limit
E132 low gas pressure
E132 flue or condensate blocked.
For
mains supply
230V signals, connect the white lead into X1 brown wire
to L (1) and blue wire N (2).
Connect the opposite end of the cable into terminal 17 live, and terminal 18
neutral, as shown.
Contacts on X1 N (6) and QX21 (7) 230V can be used for the following:
Boiler flame on/Boiler demand (closed contact)
Contacts on N (4) and QX22 (5) 230V can be used for the following:
Fault errors (closed contact)
E133 flame failure
E110 temperature high limit
E132 low gas pressure
E132 flue or condensate blocked.
12.1.2.2.
Extension module configurationt
12.1.3. UIN 23579 HC EXTENSION MODULE
Line No.
Parameter
Settings
6020
Function extension module 1
Multifunctional
6030
Relay output QX21 module 1
Status information K36
6031
Relay output QX22 module 1
Alarm output K10
Summary of Contents for STRATTON MK3 Series
Page 2: ......
Page 13: ...06 02 2023 13 154 STRATTON MK3 Installation Use and Maintenance...
Page 44: ...44 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C Figure 19 Wiring diagram...
Page 45: ...06 02 2023 45 154 STRATTON MK3 Installation Use and Maintenance...
Page 149: ...06 02 2023 149 154 STRATTON MK3 Installation Use and Maintenance...
Page 150: ...150 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C...
Page 151: ...06 02 2023 151 154 STRATTON MK3 Installation Use and Maintenance...
Page 152: ...152 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C...
Page 153: ...06 02 2023 153 154 STRATTON MK3 Installation Use and Maintenance...