4.7.2. Cable ways
4.7.3. Wiring diagram
Refer to § 2.3 in the B3100 NAVISTEM manual for more information about
the terminal block connections.
Cascade flow sensor
Room sensor inputs
Cascade return sensor
Boiler flow sensor
DHW sensor
Boiler return sensor
Outdoor sensor
Flue sensor
Prog client input 0...10V
Alarm relay
Prog client dry contact input
Modulating pump
Figure 18 - Packing glands
Cable
Terminal strips
Copper conductor
cross-section
Power supply
Power supply
3 x 1,5 mm²
Power
QX1, QX2, QX3
3 x 1 mm²
Signals
BX2, BX3, B3, B9, H1, H5,
UX2, UX3, ambient temperature sensors
2 x 0,5 mm²
4.7.4. Connections to terminals
To connect the NAVISTEM B3100 boiler controller, please refer to the
installation and user manual.
Cable passage for
signal
connections
(probes, communication
bus, etc.).
Pass example cable
Cable passages for
power
connections
(alarm report, heating
circuit circulators, DHW circulator,
mixing valves, etc.).
Boiler power supply
00U07444890-A
Summary of Contents for STRATTON MK3 Series
Page 2: ......
Page 13: ...06 02 2023 13 154 STRATTON MK3 Installation Use and Maintenance...
Page 44: ...44 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C Figure 19 Wiring diagram...
Page 45: ...06 02 2023 45 154 STRATTON MK3 Installation Use and Maintenance...
Page 149: ...06 02 2023 149 154 STRATTON MK3 Installation Use and Maintenance...
Page 150: ...150 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C...
Page 151: ...06 02 2023 151 154 STRATTON MK3 Installation Use and Maintenance...
Page 152: ...152 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C...
Page 153: ...06 02 2023 153 154 STRATTON MK3 Installation Use and Maintenance...