30 / 154
STRATTON MK3 - Installation, Use and Maintenance
00U07428680-C
4.3.5. FLUE TERMINATION POSITION
IMPORTANT INFORMATION
Install the flue in accordance to BS 5440:1 2008 Position the terminal, so
the products of combustion do not cause a nuisance. The flue is secured in
the wall using either sand and cement or heatproof silicone. The flue must
be supported by a bracket every meter of flue length and at every change of
direction.
Due to the high efficiency pluming will occur. For this reason, vertical
termination is recommended, and in any case, terminal positions which could
cause problems should wherever possible be avoided.
Care should be taken in the case of large multiple boiler installations and
complying with the requirements of the Clean Air Act. The information below
is extracted from BS. 5440 Pt. 1 and is for boilers with heat inputs not
exceeding 70kW nett, and the latest Building Regulation Part J. Detailed
reference should still be made to these standards. In IE refer to I.S. 813:2002.
Table 1 - Flue Terminal Position
(1)
In addition, for temperature and structural reasons, the terminal
should not be nearer than 150 mm (fanned draught) to an opening in the
building fabric formed for the purpose of accommodating a built-in element
such as a window frame.
(2)
Where the lowest part of the terminal is fitted less than 2m above a
balcony, above ground or above a flat roof to which people have access then
the terminal MUST be protected by a purpose designed guard
Summary of Contents for STRATTON MK3 Series
Page 2: ......
Page 13: ...06 02 2023 13 154 STRATTON MK3 Installation Use and Maintenance...
Page 44: ...44 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C Figure 19 Wiring diagram...
Page 45: ...06 02 2023 45 154 STRATTON MK3 Installation Use and Maintenance...
Page 149: ...06 02 2023 149 154 STRATTON MK3 Installation Use and Maintenance...
Page 150: ...150 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C...
Page 151: ...06 02 2023 151 154 STRATTON MK3 Installation Use and Maintenance...
Page 152: ...152 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C...
Page 153: ...06 02 2023 153 154 STRATTON MK3 Installation Use and Maintenance...