06.02.2023
81 / 154
STRATTON MK3 - Installation, Use and Maintenance
Cascaded boilers
DHW production with tank with coil
Diagram
MK3-24
page 1 / 3
A. HYDRAULIC DIAGRAM
Figure 29 - MK3-24 diagram
B. REQUIRED REGULATION ACCESSORY
Quantity
Appliance reference
DHW sensor kit
1
QAZ 36
C. OPERATING DESCRIPTION
The boiler operates at the flow temperature required to produce the domestic hot water.
The heating pump must be able to operate at a constant speed to ensure the minimum flow rate that is
required by the generator.
The domestic hot water production system has its own regulator.
A sensor QAZ 36, positioned inside the storage tank and connected to the generator, informs the boiler of
the need for domestic hot water.
DHW
DHW LOOP
DCW
Minimum flow
Model (kW)
40
60
70
80
100
120
150
Minimum flow (l/min)
9,5
19,2
19,2
38,3
38,3
50,0
57,3