06.02.2023
121 / 154
STRATTON MK3 - Installation, Use and Maintenance
Line
no.
Programming
Access
Default value
Customer setting
1630
DHW load priority
M
none
1640
Anti-legionalla function
S
stop
1641
Frequency of anti-legionella operation
S
3
1642
Anti-legionella operation Day
S
Monday
1644
Time of anti-legionella operation
S
05:00
1645
Anti-legionella operation setpoint (1640)
S
55 °C
1646
Duration the legionella operation set point is
maintained
S
30 min
1647
Circulation pump operation during legionella function
S
on
1660
DHW circulation pump release
S
DHW release
1662
Continuous circ. pump
S
no
1663
DHW circulation setpoint
S
45 °C
1680
DHW rate switching
S
stop
Consumer circuit 1
1859
Cons request output setpoint T°
U
60 °C
1874
DHW load priority
S
no
1875
Excess heat absorption
S
1
1878
With storage tank
S
no
1880
With prim regul./primar pump
S
no
Consumer circuit 2
1909
Cons request output setpoint T°
M
60 °C
1924
S
no
1925
Excess heat absorption
S
on
1928
With storage tank
S
no
1930
With prim regul./primar pump
S
no
Consumer circuit 3
1959
Flow setpoint T°
M
70 °C
1975
Excess heat absorption
S
1
1978
With storage tank
S
no
1980
With prim regul./primar pump
S
no
Pool
2056
Boiler setpoint
S
22 °C
Pre-regulator/supply pump
2110
Min. start temperature limitation pre-regulator
S
8 °C
2111
Max. start temperature limitation pre-regulator
S
80 °C
2130
Mixing valve setpoint over-value Pre-regulator
S
7 °C
2150
Pre-regulator/supply pump
S
after buffer tank
Boiler
2203
Hot release oil/gas below external temp.
S
0 °C
2210
Minimum limitation boiler temperature
S
8 °C
2212
Maximum limitation boiler temperature
S
85 °C
2214
Boiler setpoint in manual mode
U
60 °C
2217
Frost protection setpoint
S
7 °C
2243
Minimum burner pause time
S
5 min
2250
Pump stop timer
S
5 min
Summary of Contents for STRATTON MK3 Series
Page 2: ......
Page 13: ...06 02 2023 13 154 STRATTON MK3 Installation Use and Maintenance...
Page 44: ...44 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C Figure 19 Wiring diagram...
Page 45: ...06 02 2023 45 154 STRATTON MK3 Installation Use and Maintenance...
Page 149: ...06 02 2023 149 154 STRATTON MK3 Installation Use and Maintenance...
Page 150: ...150 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C...
Page 151: ...06 02 2023 151 154 STRATTON MK3 Installation Use and Maintenance...
Page 152: ...152 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C...
Page 153: ...06 02 2023 153 154 STRATTON MK3 Installation Use and Maintenance...