Error
Correct
Outdoor unit electrical wiring diagram
Power Wiring Terminal
Power Wiring Terminal
Wierd-Controller line
Communication line
Ground wire
Power cord
Power Wiring Distribution Hole
Connecting the Wired-Controller
Fixing the power line with a wire clip
Fixing the communication line and
Wired-controller line with a wire clip
Fixing the communication
line and Wired-controller
line with a wire clip
Fixing the power line
with a wire clip
Power lines and
communication lines
need to be flame
retardant and high
temperature resistant
wire wrap
Connecting the
Communication line
Power lines and communication
lines need to be flame retardant
and high temperature resistant
wire wrap
Communication line
Wierd-Controller line
Water pipe
Water pipe
Pump wire
Ground wire
Power cord
Power line
Water pipe
When using a single terminal without terminal, the terminal
can not be directly used without flux. Otherwise, it will cause
abnormal heating of terminal crimping part. If a single core
wiring is used in the wiring, it can be connected directly in the
manner shown in the diagram.