86
[64] CT current too high
Re-connect
Check if wire between
connecting board and module is
connected normally
Check if CT wire is conductive
If temperature on top of fixed
frequency compressor is too
high
If there is air into the system
If there is clogged, motor is bad
Replace compressor
Replace wire
Recharge refrigerant
Fix the system
If normal after
replacing CT detector
Replace PCB
If AC
contactor work
N
Y
Y
Y
N
N
N
N
Y
Y
N
Y