[113] Protection of overload
Improve power supply circuit
Check if voltage of power
supply is normal
Check if wire of electric box is
correct
If compressor is normal
(compressor coil resistor,
insulation)
If power module is normal
Compress load too
much, check the
reason
Correct the wiring due to
diagram
Replace compressor
Replace power module
N
Y
Y
Y
Y
N
N
N