83
[43] Discharging temp. sensor Td too low protection
Replace the sensor
If the sensor characteristic
is correct
If the terminal of
sensor is fixed well
In cooling mode, when the
indoor unit off if the EEV can't
completely close
Check if refrigerant is too much
Reconnect
Replace of adjustment the
indoor unit EEV
Recharge refrigerant
N
Y
Y
N
N
Y
Y