88
[75-0, 75-4] Pressure difference between high pressure and low pressure is abnorma
Re-connect
Check if high/ low pressure
sensor is connected well
Check if compressor wire is
connected normally
If wire of inverter compressor
are connected oppositely
If 4-way valve is interconnected
Measure if there is voltage U, V,
W of compressor by multimeter,
and if it is normal
Replace inverter compressor
Correct compressor
wire
Correct compressor wire
Replace 4-way valve
Replace inverter module
N
Y
Y
Y
N
N
N
N
Y
Y