56
Basic programming setup
Single bottle
6-A.
Select either Stop After Last Bottle or Run Continuously? Stop After Last Bottle
mode stops the program when the sample is deposited into the last bottle. Run
Continuously mode continues running until it is manually stopped.
6-B.
Press
ACCEPT
to continue to Liquid Sensor setup.
Multiple bottle sets
Multiple bottle applications use a distributor arm to automatically aim the sample intake
tubing into the proper bottle. Multiple bottle sets deliver each sample to all bottles or
deliver each sample into individual bottles or a subset of bottles.
6-A.
Select
YES
or
NO
for Deliver Each Sample to All Bottles.
If
NO
is selected:
a.
Select Samples per Bottle or Bottles per Sample.
Example 1:
Samples per bottle
•
Bottles—8
•
Sample collection; time-proportional; sampling interval—30 min.
•
Sample distribution; deliver each sample to all bottles?— No
Samples per bottle— Yes
Number of samples per bottle— 3
•
Sample volume—100 mL
Every 30 minutes a sample is initiated. A 100 mL sample is drawn into bottle #1, 30
minutes later a second sample is drawn into bottle #1, 30 minutes later a third sample
is drawn into bottle #1. Thirty minutes later the distributor arm advances to bottle #2
and a 100 mL sample is drawn into bottle #2. The sequence continues until all bottles
are filled. Each bottle receives three samples before the distributor moves to the next
bottle.
Example 2:
Bottles per sample
•
Bottles—4
•
Sample collection; timed proportional; sampling interval—30 min.
11:00 AM 21 - APR - 01
SAMPLE DISTRIBUTION
ACCEPT
RUN MODE:
CHANGE
CHOICE
RUN CONTINUOUSLY
CANCEL
CHOICES: CONTINUOUS, STOP AFTER LAST
11:00 AM 21 - APR - 01
SAMPLE DISTRIBUTION
ACCEPT
DELIVER EACH SAMPLE TO
ALL BOTTLES?
CHANGE
CHOICE
CANCEL
NO
CHOICES: YES, NO
Goodnal STP ST041 Pre Treatment (Sigma 900 MAX All Weather Refrigerated Sampler) Vendor Manual
Q-Pulse Id VM373
Active 29/10/2013
Page 56 of 122