Installation Manual
Neocean IX1000 Network Storage System
Chapter 3 Installing an IX1000
3-21
not contact any heat source, sharp point or sharp edge. Use high temperature
cables near a heat source.
z
For a wiring terminal fixed by means of threads, the screw or nut should be
securely fastened, and anti-loosing parts should be employed, as shown in
(1 ) (1) (2) (3 )
(1) Flat washer
(2) Spring washer
(3) Nut
Figure 3-28
Cable fixing example
z
When using a stiff power cable, fix it near the wiring terminal prevent stresses on
the terminal and the cable;
z
Do not use tapping screws to fasten a wiring terminal
z
The power cables of the same type and in the same direction should be bundled
together and kept neatly and straight in the bundle
lists the requirements on cable bundling with cable ties.
Table 3-3
Tie-binding parameters
Cable bundle diameter (mm)
Space between cable ties (mm)
10 mm (0.4 in.)
80 mm to 150 mm (3.2 in. to 5.9 in.)
10 mm to 30 mm (0.4 in. to 1.2 in.)
150 mm to 200 mm (5.9 in. to 7.9 in.)
30 mm (1.2 in.)
200 mm to 300 mm (7.9 in. to 11.8 in.)
z
Knots cables or cable bundles are now allowed.
z
The metal part of terminals in a crimped cold-pressed terminal block (such as an
air breaker) must not extrude outside the terminal block.
3.11 Verifying the Installation