![GW Instek GDS-1000B Series Programming Manual Download Page 129](http://html1.mh-extra.com/html/gw-instek/gds-1000b-series/gds-1000b-series_programming-manual_2280038129.webp)
COMMAND DETAILS
129
Return parameter
Returns the trigger slope.
Example
:TRIGger:DELay:SLOP FALL
Sets the trigger slope to falling.
:TRIGger:DELay:TYPe
Description
Sets or queries the trigger delay type.
Syntax
:TRIGger:DELay:TYPE {TIMe | EVENt | ?}
Related
commands
:TRIGger:TYPe
Parameter
TIMe
Sets the delay type to time.
EVENt
Sets the delay type to event.
Return parameter
Returns the trigger delay type.
Example
:TRIGger:DELay:TYPe TIMe
Sets the delay type to time delay.
:TRIGger:DELay:TIMe
Description
Sets or queries the delay time value.
Syntax
:TRIGger:DELay:TIMe {<NRf> | ?}
Related
commands
:TRIGger:DELay:TYPe
Parameter
<NRf>
Delay time (1.00E-8~1.00E+1)
Return parameter <NR3>
Returns the delay time.
Example
:TRIGger:DELay:TIMe 1.00E-6
Sets the delay time to 1us.
:TRIGger:DELay:EVENt
Description
Sets or queries the number of events for the event
delay trigger.
Set
Query
Set
Query
Set
Query