ASR-2000 Series User Manual
110
Using External Control I/O
Overview
The External Control I/O is primarily used to
control ASR-2000 externally by using the logic
signal. More than that, it is able to monitor
Sequence function status remotely with ease.
Specification
Control
input
High level: +2.2 V or higher
Low level: +1.0 V or lower
Non-destructive maximum input: +7 V
/ -5 V
Input Impedance: Pulled up to
+5 V with 47 kΩ
Status
output
Output level: 0 / +5 V
Output Impedance: 100
Ω
Pin Assignment
Check the table below for definition of each pin.
Pin No. I/O
Function
Remark
1
Output
Power source on/off status 0: OFF, 1: On
2
Output
The output on/off status
0: OFF, 1: On
3
Output
IRMS / IPK / Power Limit
0: OFF, 1: On
4
Output
Software busy status
0: Normal, 1: Busy
5
Output
Sequence sync output 0
6
Output
Sequence sync output 1
7
Output
Undefined output 0
8
Output
Undefined output 1
9
GND
10
Input
Undefined input 0
11
Input
Output off
Falling edge detection
12
Input
Output on
Falling edge detection
13
Input
Sequence start
Falling edge detection
14
Input
Sequence stop
Falling edge detection
15
Input
Sequence hold
Falling edge detection
16
Input
Sequence branch 1
Falling edge detection
17
Input
Sequence branch 2
Falling edge detection
18
GND
19
Output
+5 V
50 mA or less
Summary of Contents for ASR-2000 Series
Page 1: ...Programmable AC DC Power Source ASR 2000 Series USER MANUAL ISO 9001 CERTIFIED MANUFACTURER ...
Page 11: ...GETTING STARTED 11 ...
Page 130: ...ASR 2000 Series User Manual 130 Example Power ON setting ...
Page 216: ...ASR 2000 Series User Manual 216 ASR 2000 Dimensions ASR 2100 2050 Scale mm ...
Page 217: ...APPENDIX 217 ASR 2100R 2050R Scale mm ...
Page 218: ...ASR 2000 Series User Manual 218 ASR 2100R 2050R with GET Series Box Scale mm ...
Page 219: ...APPENDIX 219 GET 003 Series Box GET 004 Series Box ...