Specifications
Residual Current Monitor
0x8280
0x82cf
Input Registers
Bank Power Source Select
0x000
0x00f
Holding Registers
Fan Mode
0x010
0x01f
Holding Registers
This chapter is general for all Gude devices. Depending on the device type, some
ports or certain sensors are not available.
The Unit-ID is ignored because the device is uniquely identified by its IP address.
Supported Modbus TCP Functions
Function
Request Code
Read Coils
0x01
Read Discrete Inputs
0x02
Write Single Coil
0x05
Write Multiple Coils
0x0f
Read Input Registers
0x04
Read Holding Registers
0x03
Write Holding Register
0x06
Write Multiple Holding Registers
0x10
Read Device Identification
0x2B / 0x0E
Coils
Device Resource
Start
End
Device Function
Power/Output/eFuse
0x000
0x3ff
Coil represens Port State
Discrete Inputs
Device Resource
Start
End
Function when set
DC Inputs
0x400
0x7ff
Input logically 1
Stop Condition active
0x800
0x800
Stop Input active
POE active
0x801
0x801
POE active
Status Power Sources
0x1000 0x100f Power Source active
OVP active (Line-Ins)
0x1010 0x101f OVP active
eFuse Error
0x1100 0x11ff
eFuse Error
Status Power Sources
Offset
EPC 8221 / 8226
0 = Bank A, 1 = Bank B
ENC 2111 / 2191
0 = Pwr1, 1 = Pwr2
ESB 7213 / 7214
0 = Pwr1, 1 = Pwr2 (only 7214)
Summary of Contents for Expert Power Control 8314
Page 2: ...2 Expert Power Control 8316 2022 GUDESystems GmbH ...
Page 5: ...Device Description ...
Page 12: ...Operating ...
Page 23: ...Configuration ...
Page 51: ...Specifications ...
Page 104: ...104 Expert Power Control 8316 2022 GUDESystems GmbH Specifications ...
Page 105: ...Support ...