83
Expert Power Control 8316
© 2022 GUDE Systems GmbH
Specifications
extsensor all show
show s all plugged sensors and fields
extsensor {port_num} {sen_field} value show
show s sensor value
6
extsensor {port_num} {sen_type} label set
"{name}"
sets sensor name to label
6
extsensor {port_num} {sen_type} label show
show s label of sensor
6
extsensor {port_num} type show
show s type of sensor
extsensor {port_num} {sen_type} {sen_field}
events set {off=0|on=1}
enables sensor events on/off
6
extsensor {port_num} {sen_type} {sen_field}
events show
show s if sensor events are enabled
6
extsensor {port_num} {sen_type} {sen_field}
events type set
"{EVT_SYSLOG=0,EVT_SNMP=1,EVT_EMAIL=2,E
VT_SMS=3,EVT_GSMEMAIL=4,EVT_BEEPER=5,E
VT_DISPLAY=6,EVT_CONSOLE=7,EVT_MQTT=8}
"
enables different event types
6
extsensor {port_num} {sen_type} {sen_field}
events type show
show s w hat event types are enabled
6
extsensor {port_num} {sen_type} {sen_field}
maxval set {num}
sets maximum value for sensor
6
extsensor {port_num} {sen_type} {sen_field}
maxval show
show s maximum value for sensor
6
extsensor {port_num} {sen_type} {sen_field}
minval set {num}
sets minimum value for sensor
6
extsensor {port_num} {sen_type} {sen_field}
minval show
show s minimum value for sensor
6
extsensor {port_num} {sen_type} {sen_field} hyst
set {num}
sets hysterese value for sensor
6
extsensor {port_num} {sen_type} {sen_field} hyst
show
show s hysterese value for sensor
6
extsensor {port_num} {sen_type} {sen_field}
publish mode set {NONE=0|INTERVAL=1|
DELTA=2|INTERV_DELTA=3}
sets publish mode
extsensor {port_num} {sen_type} {sen_field}
publish mode show
show s publish mode
extsensor {port_num} {sen_type} {sen_field}
publish mqtt retain set {OFF=0|ON=1}
sets mqtt retain
extsensor {port_num} {sen_type} {sen_field}
publish mqtt retain show
show s if mqtt retain set
extsensor {port_num} {sen_type} {sen_field}
publish timer set {num_secs}
sets publish time interval
extsensor {port_num} {sen_type} {sen_field}
publish timer show
show s publish time interval
extsensor {port_num} {sen_type} {sen_field}
publish delta set {float}
sets publish delta value
extsensor {port_num} {sen_type} {sen_field}
publish delta show
show s publish delta value
extsensor {port_num} {sen_type} {sen_field}
{BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2|
BELOWMAX=3} port set {port_num}
sets Port for Pow er Port Sw itching actions
6
extsensor {port_num} {sen_type} {sen_field}
{BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2|
BELOWMAX=3} port show
show s Port for Pow er Port Sw itching actions
6
extsensor {port_num} {sen_type} {sen_field}
{BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2|
BELOWMAX=3} state set {OFF=0|ON=1|
DISABLED=2}
sets Port state for Pow er Port Sw itching actions
6
extsensor {port_num} {sen_type} {sen_field}
{BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2|
BELOWMAX=3} state show
show s Port state for Pow er Port Sw itching
actions
6
extsensor period set {24H=0|12H=1|2H=2|1H=3|
30MIN=4}
sets sensor Min/Max measurement period
extsensor period show
show s sensor Min/Max measurement period
http
enters cmd group "http"
Summary of Contents for Expert Power Control 8314
Page 2: ...2 Expert Power Control 8316 2022 GUDESystems GmbH ...
Page 5: ...Device Description ...
Page 12: ...Operating ...
Page 23: ...Configuration ...
Page 51: ...Specifications ...
Page 104: ...104 Expert Power Control 8316 2022 GUDESystems GmbH Specifications ...
Page 105: ...Support ...