95
Expert Power Control 8316
© 2022 GUDE Systems GmbH
Specifications
Input Registers
Device Resource
Start
End
Function
Info Bereich
0x000
0x005
see table
CPU Sensor values
0x080
0x083
see table
Externe Sensoren
0x100
0x1ff
see table
Fan Level
0x200
0x20f
0 (aus) bis 3 (maximal)
Line Energy Sensors
0x400
0x39ff
see table
Port Energy Sensors
0x3a00 0x81ff
see table
Bank Energy Sensors
0x8200 0x823f see table
Power Source Sensors
0x8240 0x827f see table
Residual Current Monitor 0x8280 0x82cf see table
Info Area
Address
Width
Information
0
16-bit
Number of Ports (Relay)
1
16-bit
Number of Ports (Outlets) with
Energy Measurement
2
16-bit
Number of Banks
3
16-bit
Number of Line-In
4
16-bit
Phases per line
5
16-bit
Number of Inputs
Sensor Type Description
Address
Width
Information
0x080 to 0x083
16-bit (signed
CPU Sensor values
0x100 to 0x1ff
16-bit (signed)
external Sensors
0x400 to 0x39ff
32-bit (signed)
Line Energy Sensors
0x3a00 to 0x81ff
32-bit (signed)
Port Energy Sensors
0x8200 to 0x823f
16-bit (signed)
Bank Energy Sensors
0x8240 to 0x827f
16-bit (signed)
Power Source Energy Sensors
0x8280 to 0x82cf
16-bit (signed)
Residual Current Monitor
CPU Sensor Values
Offset
Sensor Field
Unit
0
Vsystem
0.01 V
1
Vaux
0.01 V
2
Vmain
0.01 V
3
CPU Temperature
0.1 °C
External Sensors:
The measured value of the external sensors are coded as fixed point arithmetic. For a
factor of e.g. 0.1 in the unit the value must be divided by 10 in order to reach the real
measured value. A value of 0x8000 means that no sensor is plugged into the corres-
ponding port, or the corresponding field in the sensor is not available. The formula for the
address is (the port numbers start at zero):
Summary of Contents for Expert Power Control 8314
Page 2: ...2 Expert Power Control 8316 2022 GUDESystems GmbH ...
Page 5: ...Device Description ...
Page 12: ...Operating ...
Page 23: ...Configuration ...
Page 51: ...Specifications ...
Page 104: ...104 Expert Power Control 8316 2022 GUDESystems GmbH Specifications ...
Page 105: ...Support ...