60
Expert Power Control 8316
© 2022 GUDE Systems GmbH
Specifications
180.0
epc8314Pow erApparent
.97.1.5.1.2.1.10.x
Integer32
RO
L Line Mean Apparent Pow er
epc8314Pow erReactive
.97.1.5.1.2.1.11.x
Integer32
RO
L Line Mean Reactive Pow er
epc8314AbsEnergyReactive
.97.1.5.1.2.1.12.x
Unsigned32
RO
Absolute Reactive Energy counter.
epc8314AbsEnergyActiveResetta
ble
.97.1.5.1.2.1.13.x
Unsigned32
RW
Resettable Absolute Active Energy counter. Writing '0' resets all
resettable counter.
epc8314AbsEnergyReactiveReset
table
.97.1.5.1.2.1.14.x
Unsigned32
RO
Resettable Absolute Reactive Energy counter.
epc8314ResetTime
.97.1.5.1.2.1.15.x
Unsigned32
RO
Time in seconds since last Energy Counter reset.
epc8314Forw EnergyActive
.97.1.5.1.2.1.16.x
Unsigned32
RO
Forw ard Active Energy counter.
epc8314Forw EnergyReactive
.97.1.5.1.2.1.17.x
Unsigned32
RO
Forw ard Reactive Energy counter.
epc8314Forw EnergyActiveResett
able
.97.1.5.1.2.1.18.x
Unsigned32
RO
Resettable Forw ard Active Energy counter.
epc8314Forw EnergyReactiveRes
ettable
.97.1.5.1.2.1.19.x
Unsigned32
RO
Resettable Forw ard Reactive Energy counter.
epc8314RevEnergyActive
.97.1.5.1.2.1.20.x
Unsigned32
RO
Reverse Active Energy counter.
epc8314RevEnergyReactive
.97.1.5.1.2.1.21.x
Unsigned32
RO
Reverse Reactive Energy counter.
epc8314RevEnergyActiveResetta
ble
.97.1.5.1.2.1.22.x
Unsigned32
RO
Resettable Reverse Active Energy counter.
epc8314RevEnergyReactiveResett
able
.97.1.5.1.2.1.23.x
Unsigned32
RO
Resettable Reverse Reactive Energy counter.
epc8314LineSensorName
.97.1.5.1.2.1.100.x
OCTETS
RW
A textual string containing name of a Line Sensor
epc8314NTPTimeValid
.97.1.5.15.1.0
INTEGER
RO
Show if valid Time is received
epc8314NTPUnixTime
.97.1.5.15.2.0
Unsigned32
RO
show received NTP time as unixtime (secs since 1 January 1970)
epc8314NTPLastValidTimestamp
.97.1.5.15.3.0
Unsigned32
RO
show seconds since last valid NTP timestamp received
epc8314SensorIndex
.97.1.6.1.1.1.x
Integer32
RO
None
epc8314TempSensor
.97.1.6.1.1.2.x
Integer32
RO
actual temperature
epc8314HygroSensor
.97.1.6.1.1.3.x
Integer32
RO
actual humidity
epc8314InputSensor
.97.1.6.1.1.4.x
INTEGER
RO
logical state of input sensor
epc8314AirPressure
.97.1.6.1.1.5.x
Integer32
RO
actual air pressure
epc8314Dew Point
.97.1.6.1.1.6.x
Integer32
RO
dew point for actual temperature and humidity
epc8314Dew PointDiff
.97.1.6.1.1.7.x
Integer32
RO
difference betw een dew point and actual temperature (Temp -
Dew Point)
epc8314ExtSensorName
.97.1.6.1.1.32.x
OCTETS
RW
A textual string containing name of a external Sensor
Summary of Contents for Expert Power Control 8314
Page 2: ...2 Expert Power Control 8316 2022 GUDESystems GmbH ...
Page 5: ...Device Description ...
Page 12: ...Operating ...
Page 23: ...Configuration ...
Page 51: ...Specifications ...
Page 104: ...104 Expert Power Control 8316 2022 GUDESystems GmbH Specifications ...
Page 105: ...Support ...