59
Expert Power Control 8316
© 2022 GUDE Systems GmbH
Specifications
4.6.1
Device MIB 8314
Below is a table of all device-specific OID 's which can be accessed via SNMP. In the
numerical representation of the OID the prefix " 1.3.6.1.4.1.28507 " (Gude Enterprise
OID) was omitted at each entry in the table to preserve space. The example for a com-
plete OID would be "1.3.6.1.4.1.28507.64.1.1.1.1". A distinction is made in SNMP OID 's
in between tables and scalars. OID scalar have the extension ".0" and only specify a
value. In SNMP tables the "x" is replaced by an index (1 or greater) to address a value
from the table.
Name
OID
Type
Acc.
Description
epc8314TrapCtrl
.97.1.1.1.1.0
Integer32
RW
0 = off 1 = Ver. 1 2 = Ver. 2c 3 = Ver. 3
epc8314TrapIPIndex
.97.1.1.1.2.1.1.x
Integer32
RO
A unique value, greater than zero, for each receiver slot.
epc8314TrapAddr
.97.1.1.1.2.1.2.x
OCTETS
RW
DNS name or IP address specifying one Trap receiver slot. A port can
optionally be specified: 'name:port' An empty string disables this slot.
epc8314portNumber
.97.1.3.1.1.0
Integer32
RO
The number of Relay Ports
epc8314PortIndex
.97.1.3.1.2.1.1.x
Integer32
RO
A unique value, greater than zero, for each Relay Port.
epc8314PortName
.97.1.3.1.2.1.2.x
OCTETS
RW
A textual string containing name of a Relay Port.
epc8314PortState
.97.1.3.1.2.1.3.x
INTEGER
RW
current state a Relay Port
epc8314PortSw itchCount
.97.1.3.1.2.1.4.x
Integer32
RO
The total number of sw itch actions ocurred on a Relay Port. Does not
count sw itch commands w hich w ill not sw itch the ralay state, so just
real relay sw itches are displayed here.
epc8314PortStartupMode
.97.1.3.1.2.1.5.x
INTEGER
RW
set Mode of startup sequence (off, on , remember last state)
epc8314PortStartupDelay
.97.1.3.1.2.1.6.x
Integer32
RW
Delay in sec for startup action
epc8314PortRepow erTime
.97.1.3.1.2.1.7.x
Integer32
RW
Delay in sec for repow er port after sw itching off
epc8314PortResetDuration
.97.1.3.1.2.1.8.x
Integer32
RW
Delay in sec for turning Port on again after Reset action
epc8314ActivePow erChan
.97.1.5.1.1.0
Unsigned32
RO
Number of suppported Pow er Channels.
epc8314Pow erIndex
.97.1.5.1.2.1.1.x
Integer32
RO
Index of Pow er Channel entries
epc8314ChanStatus
.97.1.5.1.2.1.2.x
Integer32
RO
0 = data not active, 1 = data valid
epc8314AbsEnergyActive
.97.1.5.1.2.1.3.x
Unsigned32
RO
Absolute Active Energy counter.
epc8314Pow erActive
.97.1.5.1.2.1.4.x
Integer32
RO
Active Pow er
epc8314Current
.97.1.5.1.2.1.5.x
Unsigned32
RO
Actual Curent on Pow er Channel.
epc8314Voltage
.97.1.5.1.2.1.6.x
Unsigned32
RO
Actual Voltage on Pow er Channel
epc8314Frequency
.97.1.5.1.2.1.7.x
Unsigned32
RO
Frequency of Pow er Channel
epc8314Pow erFactor
.97.1.5.1.2.1.8.x
Integer32
RO
Pow er Factor of Channel betw een -1.0 and 1.00
epc8314Pangle
.97.1.5.1.2.1.9.x
Integer32
RO
Phase Angle betw een Voltage and L Line Current betw een -180.0 and
Summary of Contents for Expert Power Control 8314
Page 2: ...2 Expert Power Control 8316 2022 GUDESystems GmbH ...
Page 5: ...Device Description ...
Page 12: ...Operating ...
Page 23: ...Configuration ...
Page 51: ...Specifications ...
Page 104: ...104 Expert Power Control 8316 2022 GUDESystems GmbH Specifications ...
Page 105: ...Support ...