GST-IFP8 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 43
6.3.4 Commissioning
Choosing “4” in the screen of Fig. 6-20 will enter the menu for commissioning.
FAR:OK FPE:DIS OTS:OK 20:44:30
*******************************************
*COMMISSIONING*
1.DEVICE LEARN
2.DUPLICATED ADDRESS CHECK
3.MODIFY ADDRESS
4.MODIFY DEVICE SENSITIVITY
5.COMMISSION IN ANALOG MODE
6.COMMISSION IN DIGITAL MODE
7.SYSTEM INITIALIZATION
8.NETWORK SCAN
Fig. 6-32
Choosing
“1” in the above screen can register all loop devices.
Choosing
“2” can check loop devices with duplicated addresses, and find out if the
detector device types are in compliance with originally defined. If not, a fault message
will appear.
Choosing
“3” in the above screen will access the menu for modifying device address, as
shown in Fig. 6-33.
FAR:OK FPE:DIS OTS:OK 20:44:30
*******************************************
*MODIFY ADDRESS*
按“
ENTER
”键
Loop:01 Address(1-242):001
FAR:OK FPE:DIS OTS:OK 20:44:30
*******************************************
*MODIFY ADDRESS*
Loop:01 Address(1-242):001
USER CODE:001
SERIAL NO:01000000
NEW CODE:001
Fig. 6-33