GST-IFP8 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 12
connected cable is in short or open circuit.
ALARM ROUTING:
It
outputs when there is fire alarm and gives fault signals when
connecting line is shorted or opened.
FEED BACK:
Feedback signal input for alarm routing devices. It gives fault signal
when connecting line is shorted or opened.
REPEATER:
Connecting with repeater panel.
FAULT OUTPUT:
Fault relay is closed in normal condition,
and it’s disconnected in
fault condition.
J1:
Ground fault terminal for power supply board. The FACP reports ground fault
when it
’s shorted.
4.4.3.1 Connection of OUTPUT TO SOUNDER
Connection of OUTPUT TO SOUNDER port is shown in Fig. 4-4.
Fig. 4-4
A 4.7
kΩ resistor is connected at terminal OUTPUT TO SOUNDER as factory default.
Please remove it and keep it well before connection. Connect the loop in correct polarity
and add the resistor to the end of the line.
NOTE: The sounder strobes are polarity-sensitive. Note polarity in connection.
The maximum current of the circuit depends on the number of sounder strobes.
Do not overload.
4.4.3.2 Connection of OUTPUT TO FPE.
Connection of terminal OUTPUT TO FPE is shown in Fig. 4-5.
Fig. 4-5
A 4.7kΩ resistor is connected to the terminal OUTPUT TO FPE as factory default.
Please remove it and keep it well before connection. Connect the loop in correct polarity
and add the resistor to the end of the line.
NOTE: FPEs are polarity-sensitive. Note polarity in connection. The maximum
current of the circuit depends on the number of FPE. Do not overload.
Sounder
Diode
End of Line
Resistor
4.7kΩ
OUTPUT TO SOUNDER
Diode
Sounder
F.P.E.
End of Line
Resistor 4.7kΩ
Diode
Diode
F.P.E.
OUTPUT TO FPE