GST-IFP8 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 30
6.2.3 Printer Setup
Choosing 3 on the screen shown in Fig. 6-1 will enter the screen for printer setup, as in
Fig. 6-11. On this screen,
“1” means printing is disabled, “2” means only fire alarm
messages are to be printed, and
“3” means history log being browsed can be printed out
by choosing
ENTER
when browsing history log.
FAR:OK FPE:DIS OTS:OK 20:44:30
*******************************************
*PRINTER SETUP*
1.DISABLE
2.Only Fire
3.All History
Fig. 6-11
6.2.4 Delay Mode
Choosing 4 on the screen shown in Fig. 6-1 will enter the screen for delay mode setup,
as in Fig. 6-12.
FAR:OK FPE:DIS OTS:OK 20:44:30
*******************************************
*DELAY MODE SETUP*
1.Disable
2.Enable
Fig. 6-12
Choosing
“1. Disable” in the above screen, delay output of all output-type devices is not
allowed, and the FACP enters night mode compulsorily. If alarm dependency Type A or
Type B is set and the condition for dependency is not met within the pre-alarm delay
period, the pre-alarm will be automatically cancelled.
Summary of Contents for GST-IFP8