
GST-IFP8 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 42
FAR:OK FPE:DIS OTS:OK 20:44:30
*******************************************
*LOCAL OUTPUT SETUP*
SOUNDERA mode(0-2):0-on one fire
F.P.E.A mode(0-2):0-on one fire
ALARM ROUTINGA mode(0-2):0-on one fire
DELAY TIME:[ ] *10SEC-IN DELAY MODE
Fig. 6-30
Output mode options 0 to 2:
0: Output will be triggered on one fire alarm signal
1: Output will be triggered on fire alarm signals from more than 1 device (which may
be from different zones).
2: Output will be triggered on C&E setup.
The delay time cannot be set for F.P.E.A , which would always output immediately.
6.3.3 Working State Setup
Choosing “3” on the screen in Fig. 6-20 will access working state setup menu. As shown
in Fig. 6-31, the FACP can be optionally set up as COMMISSION or MONITORING only.
FAR:OK FPE:DIS OTS:OK 20:44:30
*******************************************
*WORKING STATE SETUP*
1.COMMISSION
2.MONITORING
Fig. 6-31
Summary of Contents for GST-IFP8
Page 1: ......