8.7.57 Dry-running protection (4.4.1)
Fig. 108
Dry-running protection
Description
Dry-running protection is one of the most important monitoring
functions, as the bearings and the shaft seal may be damaged if
the pumps run dry. We thus always recommend that you use dry-
running protection.
The function is based on monitoring of the inlet pressure or the
level in a possible tank or pit on the inlet side.
Level switches, pressure switches or analog sensors signalling
water shortage at a set level can be used.
There are three different methods for detection of water shortage:
• Pressure switch on inlet manifold or float switch/electrode
relay in the supply tank. See section
.
• Measurement of inlet pressure in the inlet manifold by means
of an analog pressure transmitter. See section
8.7.59 Measurement, inlet pressure (4.4.1.2)
.
• Measurement of level in the supply tank by means of an
analog level transmitter. See section
.
Setting via the operating panel
• Settings > Monitoring functions > Dry-running protection >
Select method.
8.7.58 Pressure/level switch (4.4.1.1)
Fig. 109
Pressure/level switch
Description
The function is primarily used in booster applications. Dry-running
protection can take place by means of a pressure switch on the
inlet manifold or a level switch in a tank on the inlet side.
When the contact is open, CU 352 registers water shortage after
a time delay of approximately 5 seconds. You can set whether the
indication is to be just a warning or an alarm stopping the pumps.
You can set restarting and resetting of alarms to be automatic or
manual.
Setting range
• Selection of digital input for the function.
• Reaction in case of water shortage: Alarm + stop.
• Restarting: Manual or Auto.
Setting via the operating panel
• Settings > Monitoring functions > Dry-running protection >
Pressure/level switch > Go to setting of digital input. Display
appears.
1. Set the input to dry-running protection.
2. Press [Back].
3. Select:
• Warning or Alarm + stop.
• Manual or Auto.
Factory setting
The setting is done in the startup wizard and depends on the
application.
Summary of Contents for Control MPC 2000 Series
Page 1: ...Control MPC Installation and operating instructions GRUNDFOS INSTRUCTIONS...
Page 2: ...2...
Page 394: ...CN 394 8 3 CU 352 8 4 1 15 6 PV SP H G A MPC E I GENI RS 485 B D E F A B C D E F G H I C 64...
Page 411: ...CN 411 8 7 16 4 2 3 55 1 0 8 7 17 4 2 4 56 24 CU 352 1 2 3 03 00...
Page 412: ...CN 412 8 7 18 4 2 5 57 1 2 3 4 8 7 19 4 2 7 58 8 7 20 4 2 8 1 2 3...
Page 416: ...CN 416 2 Qmin 69 1 8 7 28 4 3 7 2 3 4 70 1 8 7 30 4 3 8 2 3 4 2 71 5 3 15 0 25 0 6 10 25 30 50...
Page 423: ...CN 423 8 7 39 4 3 14 1 87 MPC S MPC S 100 25 100 8 7 40 4 3 14 2 88 100 100 1 70...
Page 430: ...CN 430 8 7 53 4 3 27 1 4 104 1 4 1 2 1 4 1 1 2 2 3 4 8 7 54 4 3 28 105 8 1 2 3...
Page 433: ...CN 433 8 7 59 4 4 1 2 110 8 7 30 4 3 8 1 2 3 4 5 8 7 60 4 4 1 3 111 8 7 30 4 3 8 1 2 3 3 4 5...
Page 434: ...CN 434 8 7 61 4 4 2 112 CU 352 1 2 3 8 7 62 4 4 3 113 CU 352 8 7 14 4 2 1 1 2...
Page 438: ...CN 438 8 7 68 4 4 10 120 1 2 8 7 69 4 4 11 121 CU 352 NRV NRV 1 2 G H I J MGE MPC E...
Page 439: ...CN 439 8 7 70 1 2 4 4 13 4 4 14 122 1 2 CU 352 1 2 3 4 123 1 2 3 4 124 1 2 3 4 5 125...
Page 447: ...CN 447 9 9 1 9 2 CU 352 CU 352 12 10 5 0 20 mA 4 20 mA CU 352...
Page 452: ...Arabic AR 452 20 0 20 4 CU 352...
Page 518: ...Arabic AR 518 O26 O27 O28 CUE EC Control MPC LC Control MPC F E B A Cont r ol MPC...