English (GB)
55
Fig. 94
Reading of power, Q0, 50 % speed (Grundfos Product
Center)
Fig. 95
Reading of rated power Pnom (Grundfos Product
Center)
Setting via the operating panel
• Settings > Secondary functions > Pump curve data.
• Select and set:
– Rated flow rate Qnom
– Rated head Hnom
– Max. head Hmax
– Max. flow rate Qmax
– Power, Q0, 100 % speed
– Power, Q0, 50 % speed
– Rated power Pnom.
8.7.45 Control source (4.3.20)
Fig. 96
Control source
Description
The system can be remote-controlled via an external bus
connection (option). See section
For further
information, see section
Select the control source, that is either CU 352 or the external
bus connection.
Setting via the operating panel
• Settings > Secondary functions > Control source.
Factory setting
The control source is CU 352.
8.7.46 Fixed inlet pressure (4.3.22)
Fig. 97
Fixed inlet pressure
Description
The function is only used when no inlet-pressure sensor is fitted
in the system and the inlet pressure is fixed and known.
If the booster system has a fixed inlet pressure, you can enter it in
the display so that CU 352 can optimise the performance and
control of the system.
Setting range
A fixed inlet pressure can be set, and the function can be enabled
and disabled.
Setting via the operating panel
• Settings > Secondary functions > Fixed inlet pressure.
• Select: Enabled or Disabled.
• Set: Fixed inlet pressure.
Factory setting
The function is disabled.
TM
0
3
9
995
4
807
TM0
3
999
6 4
8
0
7
Qnom and Hnom are the rated duty point of the
pumps and usually the duty point with the highest
efficiency.
Power, Q0, 50 % speed
Duty point, Q0, 50 %
speed
Duty point, rated
power Pnom
Rated power Pnom
Summary of Contents for Control MPC 2000 Series
Page 1: ...Control MPC Installation and operating instructions GRUNDFOS INSTRUCTIONS...
Page 2: ...2...
Page 394: ...CN 394 8 3 CU 352 8 4 1 15 6 PV SP H G A MPC E I GENI RS 485 B D E F A B C D E F G H I C 64...
Page 411: ...CN 411 8 7 16 4 2 3 55 1 0 8 7 17 4 2 4 56 24 CU 352 1 2 3 03 00...
Page 412: ...CN 412 8 7 18 4 2 5 57 1 2 3 4 8 7 19 4 2 7 58 8 7 20 4 2 8 1 2 3...
Page 416: ...CN 416 2 Qmin 69 1 8 7 28 4 3 7 2 3 4 70 1 8 7 30 4 3 8 2 3 4 2 71 5 3 15 0 25 0 6 10 25 30 50...
Page 423: ...CN 423 8 7 39 4 3 14 1 87 MPC S MPC S 100 25 100 8 7 40 4 3 14 2 88 100 100 1 70...
Page 430: ...CN 430 8 7 53 4 3 27 1 4 104 1 4 1 2 1 4 1 1 2 2 3 4 8 7 54 4 3 28 105 8 1 2 3...
Page 433: ...CN 433 8 7 59 4 4 1 2 110 8 7 30 4 3 8 1 2 3 4 5 8 7 60 4 4 1 3 111 8 7 30 4 3 8 1 2 3 3 4 5...
Page 434: ...CN 434 8 7 61 4 4 2 112 CU 352 1 2 3 8 7 62 4 4 3 113 CU 352 8 7 14 4 2 1 1 2...
Page 438: ...CN 438 8 7 68 4 4 10 120 1 2 8 7 69 4 4 11 121 CU 352 NRV NRV 1 2 G H I J MGE MPC E...
Page 439: ...CN 439 8 7 70 1 2 4 4 13 4 4 14 122 1 2 CU 352 1 2 3 4 123 1 2 3 4 124 1 2 3 4 5 125...
Page 447: ...CN 447 9 9 1 9 2 CU 352 CU 352 12 10 5 0 20 mA 4 20 mA CU 352...
Page 452: ...Arabic AR 452 20 0 20 4 CU 352...
Page 518: ...Arabic AR 518 O26 O27 O28 CUE EC Control MPC LC Control MPC F E B A Cont r ol MPC...