Legend of terminals
Control panel enclosure Conex
®
DIA-2
•
Conex
®
DIA-2
: for installation in the control panel.
•
Sensor interface: for installation near the sensors.
10.2 Power supply connection
1. Control panel enclosure: Plug the plug strip into
the corresponding terminal strip at the rear side
of the device. Ensure correct orientation.
2. Connect the protective earth conductor (PE) to
terminal 5 (wall-mounted enclosure) or terminal
8/1 (control panel enclosure).
3. Connect the neutral conductor (N) (or the -
conductor with 24 V version) to terminal 3
(wall-mounted enclosure) or terminal 8/2 (control
panel enclosure).
4. Connect phase (L1) (or the + conductor with 24 V
version) to terminal 1 (wall-mounted enclosure)
or 8/3 (control panel enclosure).
Switch the device on and off by switching the power
supply on and off accordingly. The device itself is not
equipped with a separate on/off switch.
10.3 Relay outputs
With inductive loads (also relays and contactors),
interference suppression is necessary. If this is not
possible, protect the relay contacts using a suppressor
circuit as described below.
•
With AC voltage:
•
With DC voltage: Connect the free-wheeling
diode in parallel to relay or contactor.
Fig. 10
Suppressor circuit, DC/AC
Pos.
Description
Relays
Relay 1 + 2
Alarm
Alarm relay
–
N.O.
: normally open
–
N.C.
: normally closed
Pt100
Temperature sensor
H
2
O
Water sensor
Stop
Controller stop
(NO or NC selectable)
Outputs
Current outputs [mA]
1
Cl
2
(chlorine),
ClO
2
(chlorine dioxide),
O
3
(ozone) or
H
2
O
2
(hydrogen peroxide)
2
pH
3
T/P2: temperature / continuous
controller parameter 2
4
P1: output of continuous controller
parameter 1
Electrodes
Measuring cells, electrodes and
single-rod measuring chains
M
Measuring electrode
B/R
Reference electrode
G/C
Counter electrode
Earth
mV
pH electrode
Screen
Note
The connection of the relay outputs
depends on the application and the final
control elements used. Therefore the
connections described below should only
be considered as guidelines.
Current up to
Capacitor C
Resistor R
60 mA
10 nF, 275 V
390
Ω
, 2 W
70 mA
47 nF, 275 V
22
Ω
, 2 W
150 mA
100 nF, 275 V
47
Ω
, 2 W
1.0 A
220 nF, 275 V
47
Ω
, 2 W
Caution
Provide the relay outputs with a
corresponding backup fuse!
TM
03 72
09 281
3
+
-
DC
R
C
AC
Summary of Contents for Conex DIA-2
Page 2: ...2...
Page 456: ...RU 456 2 Conex DIA 2 1 2 pH Conex DIA 2 PID...
Page 459: ...RU 459 4 Conex DIA 2 GRUNDFOS 5 Conex DIA 2 Cl2 ClO2 O3 H2O2 pH 6 6 1 Conex DIA 2 6 2 GRUNDFOS...
Page 468: ...RU 468 10 1 2 3 Conex DIA 2 4 IP65 IP65...
Page 481: ...RU 481 11 4 1 OK Esc 10 AQC D2 D12 Cal Man Cal Man Cal Man...
Page 488: ...RU 488 11 6 11 6 1 30 1 2 Up Down OK TM03 6734 4506 1 2 2 1 P PI PID...
Page 489: ...RU 489 1 Up Down OK 2 Up Down OK 3 Up Down OK 4 Up Down OK 5 Up Down P PI PID OK...
Page 492: ...RU 492 11 6 4 PI PID 1 33 2 Man 20 20 3 4 OK Esc 5 OK Esc TM03 6715 4506 0 43 pH...
Page 493: ...RU 493 11 7 34 TM03 6737 4506 1 2 1 1 2 2 2 1...
Page 495: ...RU 495 11 8 OK 35 TM03 6738 4506 5 1 10 1 pH 2 4 1 1 1 3 1 4 1 2 0 4 A 10 A 20 A 2 3...
Page 499: ...RU 499 120 pH 50 62 pH 60 60 OK 25 C 1 2 Cal pH OK pH 3 OK 4 C F 5 OK 1 100 25 C...
Page 501: ...RU 501 11 10 1 Man 2 Up Down Man 3 0 4 Man 11 10 1 38 TM03 6721 4506 Man 1 0 100 2 0 100...
Page 503: ...RU 503 11 10 2 39 OK 11 6 3 TM03 6721 4506 Man 1 2 0 100...
Page 504: ...RU 504 12 1 a 2 pH pH 7 a 3 a 4 a b pH c pH d e 5 a 6 pH a b 7 pH a b c 8 a 11 5 8 9 a...
Page 505: ...RU 505 13 14 GRUNDFOS GRUNDFOS 15 24 GRUNDFOS...
Page 608: ...608...
Page 609: ...609...