D Installation
1 | General installation information
The installation site must offer adequate space. A foundation of a
sufficient size and adequate load carrying capacity has to be provided.
The required connections must be provided prior to the installation.
For dimensions and connection data, please refer to table C-1.
Note:
Also observe the operation manuals that have been supplied
with the optional accessories (see chapter C, 5.2) for your system
(if applicable).
1.1 Water connection
When installing the reverse osmosis system AVRO 125 TS/TL, certain
rules must always be observed. Additional recommendations are given
in order to facilitate the handling of the system. The installation
instructions described below are also illustrated in fig. D-2.
Binding rules
The installation of a reverse osmosis system AVRO 125 TS/TL
represents a major interference with the drinking water system.
Therefore, only authorised experts are allowed to install such systems.
Please observe the local installation guidelines and the general
regulations.
Install a drinking water filter (e.g. BOXER KD) upstream of the
system.
Install a system separator upstream.
Install an activated carbon filter upstream, if required.
Provide a drain connection (minimum DN 50) to discharge the
concentrate.
Note:
If the concentrate is directed to a lifting system, the delivery
rate of the lifting system should at least be 500 l/h.
Warning!
The installation site must have a floor drain. If no floor drain
is available, an adequate safety device needs to be installed (refer to
chapter C, no. 5.2 Optional accessories).
Warning!
Floor drains that discharge to a lifting system will not
work in case of a power failure.
Recommendation
Install a sample valve immediately before and after the reverse
osmosis system AVRO 125 TS/TL. This simplifies the sampling for
the regular quality control (functional check).