E32.0.02.6C-04
Manual for connection and operation of the
GIA 2000 / AAG and GIR 2002 / AAG
page 21 of 30
6.2. 2-point-controller
This chapter describes how to configure the device as a 2-point-controller and how to adjust the switching
values. This instruction demands that you selected “
2P
“ as your desired output function like it is explained in
chapter 6.1.
-
Press button 1
.
The device will be displaying “
1.on
“ (turn-on-point of switching function 1).
-
Use button 2 or button 3 to set the desired value, the device’s switching function 1 should be turning on.
-
Press button 1 to validate your selection. The display shows “
1.on
“ again.
-
Press button 1 again, the device will be displaying “
1.off
“. (turn-off-point of switching function 1)
-
Use button 2 or button 3 to set the desired value, the device’s switching function 1 should be turning off.
-
Press button 1 to validate your selection. The display shows “
1.off
“again.
-
Press button 1 again, the device will be displaying “
1.dEL
“(delay of switching function 1).
-
Use button 2 or button 3 to set the desired value
[in sec]
for the switching-delay of switching function 1.
-
Press button 1 to validate the selection. The display shows “
1.dEL
“ again.
-
When pressing button 1 again, the device will display “
1.Err
“ (preferred state of switching function 1).
-
Use button 2 or button 3 to set the desired initial state in case of an error.
Display
Preferred state of the output
Note
off
Inactive in case of an error
on
Active in case of an error
-
Press button 1 to validate the selection. The display shows “
1.Err
“ again.
-
When pressing button 1 again, the display shows “
outP
“ ('output') again.
Now you have finished the output configuration.
-
Press now button 4 to exit the output configuration menu.
6.3. Minimum/maximum-alarm
This chapter describes how to adjust the device‘s alarm boundaries for min-/max-alarm-monitoring.
This instruction demands that you selected “
AL.F1
“ as your desired output function like it is explained in
chapter 6.1.
Please note that the alarm-outputs are inverted! This means, that the output will be active when there is no alarm!
-
When pressing button 1, the device will be displaying “
AL.Hi
“. (maximum alarm-value)
-
Use button 2 or button 3 to set the desired value, the device should turn on its maximum-alarm.
-
Press button 1 to validate your selection. The display shows “
AL.Hi
“ again.
-
When pressing button 1 again, the device will be displaying “
AL.Lo
“. (minimum alarm-value)
-
Use button 2 or button 3 to set the desired value, the device should turn on its minimum-alarm
-
Press button 1 to validate your selection. The display shows “
AL.Lo
“ again.
-
When pressing button 1 again, the device will be displaying “
A.dEL
“. (delay of the alarm-function)
-
Use button 2 or button 3 to set the desired delay of the alarm-function.
Note:
The unit of the value to be set is in [sec.]. The device will turn on the alarm after the minimum
or the maximum alarm value was active for the delay-time you have set.
-
Press button 1 to validate the delay time. The display shows “
A.dEL
“ again.
-
When pressing button 1 again, the display shows “
outP
“ ('output') again.
Now you have finished the output configuration.
-
Press now button 4 to exit the output configuration menu.